Intelligent Technologies (
IT.
) D77B-DSNAP
Pub. No. MN05004001E
41
September 2002
Table 47: Assembly 105 (0x69) — D77B-DSNAP Abbreviated Motor Starter 1
Table 48: Assembly 106 (0x6A) — D77B-DSNAP Abbreviated Motor Starter 2
Table 49: Assembly 108 (0x6C) — D77B-DSNAP Motor Starter with Fault Code
Table 50: Assembly 109 (0x6D) — D77B-DSNAP Expanded Motor Starter with Fault Code
Table 51: Assembly 114 (0x72) — D77B-DSNAP Complete Status Assembly
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
At Reference Reserved CtrlFrom Net Ready
Reserved Running1 Warn
Fault
1
% Thermal Capacity
2
% FLA
3
Fault Code (Low byte only)
Byte Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
At Reference Reserved
CtrlFrom
Net
Ready
Running2 Running1 Warn
Fault
1
% Thermal Capacity
2
% FLA
3
Last Fault Code (Low byte only)
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
At Reference Reserved
CtrlFrom
Net
Ready
Reserved
Running1
Warn
Fault
1
% Thermal Capacity
2
Average Current (Low byte)
3
Average Current (High byte)
4
Last Fault Code (Low byte)
5
Last Fault Code (High byte)
Byte Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
At Reference Reserved
CtrlFrom
Net
Ready
Running2
Running1
Warn
Fault
1
% Thermal Capacity
2
Average Current (Low byte)
3
Average Current (High byte)
4
Last Fault Code (Low byte)
5
Last Fault Code (High byte)
Byte Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
At Reference Reserved
Ctrl From
Net
Ready
Running2
Running1
Warning
Fault