Intelligent Technologies (
IT.
) D77B-DSNAP
Pub. No. MN05004001E
35
September 2002
Table 33: Control Supervisor Object 0x29 — Instance 1
Attribute
Access
Data Type
Name
Value
3
Set
BOOL
Run 1
0 = False
4
Set
BOOL
Run 2
0 = False
5
Set
BOOL
Net Control
0 = Local Control
1 = Network Control
7
Get
BOOL
Running 1
0 = Other State
1 = Enabled and Run 1
8
Get
BOOL
Running 2
0 = Other State
1 = Enabled and Run 2
9
Get
BOOL
Ready
0 = Other State
1 = Ready or Enabled or Stopping
10
Get
BOOL
Faulted
0 = No Faults
1 = Fault Occurred
11
Get
BOOL
Warning
0 = No Warning
1 = Warning
12
Set
BOOL
Fault Reset
0 > 1 = Fault Reset
0 = No Action
13
Get
UINT
Fault Code
0 = No Fault
10 = Test
20 = Current Trip
21 = Thermal Overload
22 = Phase Loss
26 = Phase Imbalance
27 = Ground Fault
41 = Control Undervoltage
62 = Memory Fault
63 = Hardware Link Fault
64 = No Device Power
71 = Fail to Close Primary Contactor
72 = Fail to Open Primary Contactor
101 = Invalid Attached Device Version
102 = SCR Overt Temperature
103 = Watchdog
104 = SNAP Protocol Failure to Connect
105 = SNAP Protocol fault
106 = Temperature Sensor Fault
171 = Fail to Close Second Contactor
172 = Fail to Open Second Contactor
173 = Invalid Action Attempted
14
Get
UINT
Warning Code
0 = No Warning
29 = Underload
41 = Control Undervoltage
71 = Fail to Close Primary Contactor
72 = Fail to Open Primary Contactor
104 = SNAP Protocol Failure to Connect
171 = Fail to Close Second Contactor
172 = Fail to Open Second Contactor