LCX9000 Liquid-Cooled Drives User Manual
MN04005001E
For more information visit:
www.EatonElectrical.com
3-9
January 2007
Installation Space
Enough free space must be left above and below the drive to ensure practical and
appropriate electrical and cooling connections. The minimum dimensions are given in the
table below. No space is required to the left and right of the drive.
Figure 3-2: Installation Space
A
B
Distance to the cable connection block. Additional
space must be reserved for ferrite rings, if used.
See
Page 3-1
.
Chassis
Approximate Dimensions
in Inches (mm)
A
B
CH3
3.94 (100)
5.91 (150)
CH4
3.94 (100)
7.87 (200)
CH5
3.94 (100)
7.87 (200)
CH61
3.94 (100)
11.81 (300)
CH62
3.94 (100)
15.75 (400)
CH63
7.87 (200)
15.75 (400)
CH64
7.87 (200)
19.69 (500)
CH72
7.87 (200)
15.75 (400)
CH74
7.87 (200)
19.69 (500)