LCX9000 Liquid-Cooled Drives User Manual
x
For more information visit:
www.EatonElectrical.com
MN04005001E
January 2007
Grounding and Ground Fault Protection
The LCX9000 drive must always be grounded with a ground conductor connected to the
ground terminal.
The ground fault protection inside the drive only protects the drive against ground faults in
the motor or the motor cable. It is not intended for personal safety.
Due to the high capacity currents present in the drive, fault current protective switches may
not function properly.
Motor and Equipment Safety
CAUTION
Before starting the motor, check that the motor is mounted properly
and ensure that the machine connected to the motor allows the
motor to be started.
CAUTION
Set the maximum motor speed (frequency) according to the motor
and the machine connected to it.
CAUTION
Before reversing the motor, make sure that this can be done safely.
CAUTION
Make sure that no power correction capacitors are connected to the
motor cable.
CAUTION
Make sure that the motor terminals are not connected to mains
potential.
CAUTION
Before the Liquid-Cooled drive can be used to control the motor,
the proper functioning of the liquid-cooling system must be
ensured.