PUB 51079

 

 

D64RP14 SERIES A2 DIGITAL GROUND FAULT RELAY 

 

 

Revision 1 

May, 2005 

Page 7 

 

 

 

As indicated in the General Description, it is recommended that the ground fault TRIP LEVEL setting 

be kept as close to the charging current as possible. This will provide maximum safety for operating 

personnel and equipment protection. On resistance grounded systems, the TRIP LEVEL setting 

should be set lower than 20% of the Neutral Grounding Resistor let-through current.  

 

 

If the measured ground fault current exceeds the TRIP LEVEL setting, the output relay changes state 

after the pre-selected TRIP DELAY time.  

 

2.2.2 

GROUND FAULT TRIP DELAY TIME – DIPSWITCHES 4, 5, & 6

 

 

The ground fault TRIP DELAY time range is 0.5 - 10.0 seconds. Table 1 provides a listing of the eight 

TRIP DELAY settings, which can be made with DIPswitches 4, 5, & 6. 

 

The TRIP DELAY time begins when the ground fault trip level setting is reached or is exceeded. 

 

Set the ground fault TRIP DELAY time to provide the desired delay before the output relay changes 

state when the ground fault TRIP LEVEL setting is reached or exceeded.  

 

The setting should be selected to co-ordinate with other ground-fault devices connected on the same 

transformer secondary: set shorter than upstream devices; set longer than downstream devices. If no 

other ground-fault devices are connected, set for the shortest time. 

2.2.3 

OUTPUT RELAY OPERATING MODE - DIPSWITCHES 7 & 8

 

 

Referring to the Glossary of Terms, determine if FAILSAFE, NON-FAILSAFE, or PULSED AUTO 

RESET operation of the output relay is required. The factory setting is NON-FAILSAFE with 

DIPswitches 7 & 8 in the 

D

own position. 

 

Refer to Table 1 for DIPswitch settings for FAILSAFE and PULSED AUTO RESET operation.  

 

2.3 

OUTPUT RELAY CONTACT STATE

 

 

The output relay contact state is determined by the operating mode selected and the sensing condition 

of the D64RP14 relay. This is shown in Table 2. Use this table when deciding on field connections. 

Refer to the CONNECTIONS section.  

 

2.4 

INDICATION

 

 

 

There is one green LED on the front of the D64RP14: 

 

 

Off: 

 

No control voltage or D64RP14 defective 

 

 

Slow Flashing:  Okay, control voltage on 

 

 

Fast Blinking: 

Ground Fault Trip 

 

 

Steady On: 

Control voltage too low or D64RP14 defective 

 

 

 

2.5 

RESET 

 

 

The D64RP14 has two terminals R1 and R2 for a remote N.O. Test/Reset button. After a trip, the 

electronics remain in the tripped state until the ground fault has been cleared and the Reset button has 

been pressed, or the control voltage is removed from terminals L- & N+.  

 

 

It is 

NOT

 necessary to press the remote Test/Reset button after the ground fault has been cleared 

when the D64RP14 is set in the Pulsed Trip Auto Reset mode. In this mode the relay will reset 

automatically in 3 seconds. 

 

2.6 

GROUND FAULT TEST 

 

Double clicking the external button connected to terminals R1 and R2 invokes a relay test. A simulated 

current equal to 1.2 times the trip current set on the Trip Level DIPswitches replaces the measured 

current. After the trip delay time set on the Trip Delay DIPswitch has elapsed, the unit should trip and 

the green LED will fast blink. This procedure tests the functionality of the unit. 

Содержание Cutler-Hammer D64RP14 Series

Страница 1: ...28 South Service Road 4201 North 27th Street Burlington Ontario Milwaukee WI L7R 3Y8 53216 T2 T1 R1 R2 N L M M 11 12 13 14 24 240V AC DC CT TEST RESET N C N O METER INTERNAL 100 0 5 10 RATINGS PER IEC...

Страница 2: ...TE 7 2 4 INDICATION 7 2 5 RESET 7 2 6 GROUND FAULT TEST 7 3 INSTALLATION INSTRUCTIONS 8 3 1 MOUNTING 8 3 2 BUILT IN CURRENT TRANSFORMER 8 3 3 EXTERNAL CURRENT TRANSFORMER 8 3 4 CONNECTIONS 9 3 4 1 CON...

Страница 3: ...nding on the overall length of the cables the types of loads the quality of insulation on the phase conductors the surrounding equipment grounding cable trays junction boxes etc and the type of transf...

Страница 4: ...green LED is turned off This is in effect Auto Reset If the ground fault has not been cleared when control voltage is restored the relay will trip and the green LED will resume fast blink after 500 mi...

Страница 5: ...als N L In this condition the green LED does not light If control voltage is maintained on terminals N L after a ground fault trip the RESET button must be pressed to reset the relay after clearing th...

Страница 6: ...the D64RP14 relay is energized this can be done without having any adverse effect on the performance of the relay Please Refer to Table 1 This provides a list of the 8 DIPswitches the function of each...

Страница 7: ...NON FAILSAFE or PULSED AUTO RESET operation of the output relay is required The factory setting is NON FAILSAFE with DIPswitches 7 8 in the Down position Refer to Table 1 for DIPswitch settings for F...

Страница 8: ...actors and high power conductors and buswork CAUTION For reliable ground fault detection by the D64RP14 use one CT configuration only Built in CT or External CT i e do not pass power conductors throug...

Страница 9: ...ps 300 Volts Each screw clamp terminal will accept 26 12 AWG solid or stranded conductors The terminals are pull apart For remote metering connect a meter having a 0 10 volt movement with a 0 100 scal...

Страница 10: ...f one of the units and connect the other terminal of the button to terminals R1 of all the units in parallel 4 CATALOG NUMBERS D64RP14 Ground Fault Relay with built in 1 1 28mm CT 24 240 Volts ac or d...

Страница 11: ...de Selected on DIPswitches 7 8 Non Failsafe Failsafe Pulsed Auto Reset Functional Test A simulated current equal to 120 of the trip current set on the Trip Level DIPswitches replaces the measured curr...

Страница 12: ...ms 9711 10045 ms 9700 10032 ms 9694 10026 ms Frequency Response Range 45 65 Hz Thermal Characteristics Short Time Withstand 1000A 1 second 2000A 0 1 second Environment Operating Temperature 35 C to 6...

Страница 13: ...tromagnetic compatibility EMC for industrial process measurement and control equipment Part 4 5 Surge immunity EN 61000 4 6 Electromagnetic compatibility EMC for industrial process measurement and con...

Страница 14: ...PERATING CONDITIONS 13 14 11 12 13 14 11 12 13 14 11 12 1 CONTROL POWER OFF 2 CONTROL POWER ON 500 ms 500 ms 3 CONTROL POWER ON FAULT CURRENT ABOVE TRIP SETTING TRIP TIME NO RESET REQUEST 3 Sec Pulse...

Страница 15: ...RRENT TRANSFORMER AND PULSED TRIP AUTO RESET POWER SOURCE T2 T1 R1 R2 N L M M 11 12 13 14 24 240V AC DC CT TEST RESET N C N O METER INTERNAL 100 0 5 10 RATINGS PER IEC 60755 CT SENSOR In A I n A EXT 5...

Страница 16: ...SYSTEMS 1 Phase 2 wire 1 Phase 3 wire 3 Phase 3 wire 3 Phase 4 wire POWER SOURCE CURRENT CARRYING NEUTRAL WHEN USED 500 1 C311CT SERIES R 1M 1M START STOP O L T2 T1 R1 R2 N L M M 11 12 13 14 24 240V A...

Страница 17: ...KG PACKAGED WEIGHT 1 08 LBS 49 KG DIMENSIONS ARE IN INCHES MM IN BRACKETS FIGURE 3 DIMENSIONS AND WEIGHTS D64RP14 REAR PANEL MOUNTING DIN RAIL OR 2 SCREW 1 38 35 2 76 70 1 10 28 1 26 32 4 03 102 4 4 9...

Страница 18: ...e green IND LED should fast blink This procedure tests the functionality of the unit RESETTING THE D64RP14 AFTER GROUND FAULT TRIP TEST If the D64RP14 is in the Non failsafe or Failsafe mode manual re...

Отзывы: