PUB 51079

 

 

D64RP14 SERIES A2 DIGITAL GROUND FAULT RELAY 

 

 

Revision 1 

May, 2005 

Page 9 

 

 

 

The D64RP14 will work with Eaton’s Cutler-Hammer C311CT current transformers having a turns ratio 

of 500:1. These are epoxy molded to give exceptional mechanical properties and have high-grade 

silicon iron cores for excellent coupling characteristics.  

 

 

Refer to section 4 to select the catalog number of the C311CT current transformer with the opening 

required for the application. 

 

 

Phase conductors must be insulated for the system voltage when it is higher than 660 Volts.  

 

 

Refer to Figure 2. Pass the phase conductors through the CT window. If the neutral conductor is being 

connected downstream, it is to be passed through the window. Do not pass ground conductors 

through the CT window. In applications that require shielded wires to pass through the CT window, 

return the shields through the CT window before connecting them to ground.  

 

 

Verify that the polarity of the conductors is correct when they pass through the CT. Verify that ground 

paths do not exist that would bypass the CT.   

 

 

Position power cables in the center of the current transformer opening. Keep cables and buswork clear 

of the split on split core current transformers. 

 

 

The two secondary terminals of the external CT are to be connected to terminals T1 and T2 of the 

D64RP14. 

 

3.4 

CONNECTIONS

 

 

 

All connections to the D64RP14 are by means of two screw clamp terminals per pole (Double Row T 

Connector) rated 10 Amps, 300 Volts. Each screw clamp terminal will accept #26-12 AWG solid or 

stranded conductors.  

 

 

The terminals are pull apart.  

 

 

For remote metering connect a meter having a 0-10 volt movement with a 0-100% scale to terminals 

M+ and M-. Observe polarity when making the connections. 

 

 

 

Note

:  Terminals M+ and M- are NOT isolated from the control voltage; terminal M- is internally 

connected to terminal N-. 

 

 

If an external CT is being used, connect the two secondary terminals of the CT to terminals T1 and T2 

of the relay using 14 AWG (minimum). Twist the leads to optimise electromagnetic immunity. 

 

 

Note

:  The CT’s input terminals T1 and T2 are NOT isolated from the control voltage. If an external 

CT is used it is grounded internally via the power supply input and 

must not

 be grounded 

again externally (ground loops). 

 

 

For remote Test and Reset connect a N.O. momentary contact TEST/RESET button to terminals R1 

and R2. 

 

 

 

Note

:  Terminals R1 and R2 are NOT isolated from the control voltage; terminal R2 is internally 

connected to terminal N-. 

 

 

Connect ac or dc control power to terminals N- and L+. Observe polarity. 

 

 

In order to meet the Electromagnetic Compatibility (EMC) requirements a chassis bond is required 

between terminal N- and the nearest ground point. This distance should be kept to an absolute 

minimum. If the D64RP14 is mounted on 35 mm DIN rail a DIN rail mounted ground terminal block can 

be installed beside the relay to act as the chassis ground point.  

 

 

Refer to Figure 1, Figure 2, and Table 2. Decide on the connection of field devices to control voltage 

and output relay contact terminals by comparing the desired control of the field devices under various 

operating conditions. 

Содержание Cutler-Hammer D64RP14 Series

Страница 1: ...28 South Service Road 4201 North 27th Street Burlington Ontario Milwaukee WI L7R 3Y8 53216 T2 T1 R1 R2 N L M M 11 12 13 14 24 240V AC DC CT TEST RESET N C N O METER INTERNAL 100 0 5 10 RATINGS PER IEC...

Страница 2: ...TE 7 2 4 INDICATION 7 2 5 RESET 7 2 6 GROUND FAULT TEST 7 3 INSTALLATION INSTRUCTIONS 8 3 1 MOUNTING 8 3 2 BUILT IN CURRENT TRANSFORMER 8 3 3 EXTERNAL CURRENT TRANSFORMER 8 3 4 CONNECTIONS 9 3 4 1 CON...

Страница 3: ...nding on the overall length of the cables the types of loads the quality of insulation on the phase conductors the surrounding equipment grounding cable trays junction boxes etc and the type of transf...

Страница 4: ...green LED is turned off This is in effect Auto Reset If the ground fault has not been cleared when control voltage is restored the relay will trip and the green LED will resume fast blink after 500 mi...

Страница 5: ...als N L In this condition the green LED does not light If control voltage is maintained on terminals N L after a ground fault trip the RESET button must be pressed to reset the relay after clearing th...

Страница 6: ...the D64RP14 relay is energized this can be done without having any adverse effect on the performance of the relay Please Refer to Table 1 This provides a list of the 8 DIPswitches the function of each...

Страница 7: ...NON FAILSAFE or PULSED AUTO RESET operation of the output relay is required The factory setting is NON FAILSAFE with DIPswitches 7 8 in the Down position Refer to Table 1 for DIPswitch settings for F...

Страница 8: ...actors and high power conductors and buswork CAUTION For reliable ground fault detection by the D64RP14 use one CT configuration only Built in CT or External CT i e do not pass power conductors throug...

Страница 9: ...ps 300 Volts Each screw clamp terminal will accept 26 12 AWG solid or stranded conductors The terminals are pull apart For remote metering connect a meter having a 0 10 volt movement with a 0 100 scal...

Страница 10: ...f one of the units and connect the other terminal of the button to terminals R1 of all the units in parallel 4 CATALOG NUMBERS D64RP14 Ground Fault Relay with built in 1 1 28mm CT 24 240 Volts ac or d...

Страница 11: ...de Selected on DIPswitches 7 8 Non Failsafe Failsafe Pulsed Auto Reset Functional Test A simulated current equal to 120 of the trip current set on the Trip Level DIPswitches replaces the measured curr...

Страница 12: ...ms 9711 10045 ms 9700 10032 ms 9694 10026 ms Frequency Response Range 45 65 Hz Thermal Characteristics Short Time Withstand 1000A 1 second 2000A 0 1 second Environment Operating Temperature 35 C to 6...

Страница 13: ...tromagnetic compatibility EMC for industrial process measurement and control equipment Part 4 5 Surge immunity EN 61000 4 6 Electromagnetic compatibility EMC for industrial process measurement and con...

Страница 14: ...PERATING CONDITIONS 13 14 11 12 13 14 11 12 13 14 11 12 1 CONTROL POWER OFF 2 CONTROL POWER ON 500 ms 500 ms 3 CONTROL POWER ON FAULT CURRENT ABOVE TRIP SETTING TRIP TIME NO RESET REQUEST 3 Sec Pulse...

Страница 15: ...RRENT TRANSFORMER AND PULSED TRIP AUTO RESET POWER SOURCE T2 T1 R1 R2 N L M M 11 12 13 14 24 240V AC DC CT TEST RESET N C N O METER INTERNAL 100 0 5 10 RATINGS PER IEC 60755 CT SENSOR In A I n A EXT 5...

Страница 16: ...SYSTEMS 1 Phase 2 wire 1 Phase 3 wire 3 Phase 3 wire 3 Phase 4 wire POWER SOURCE CURRENT CARRYING NEUTRAL WHEN USED 500 1 C311CT SERIES R 1M 1M START STOP O L T2 T1 R1 R2 N L M M 11 12 13 14 24 240V A...

Страница 17: ...KG PACKAGED WEIGHT 1 08 LBS 49 KG DIMENSIONS ARE IN INCHES MM IN BRACKETS FIGURE 3 DIMENSIONS AND WEIGHTS D64RP14 REAR PANEL MOUNTING DIN RAIL OR 2 SCREW 1 38 35 2 76 70 1 10 28 1 26 32 4 03 102 4 4 9...

Страница 18: ...e green IND LED should fast blink This procedure tests the functionality of the unit RESETTING THE D64RP14 AFTER GROUND FAULT TRIP TEST If the D64RP14 is in the Non failsafe or Failsafe mode manual re...