Approved sensor manufacturers
40
CBC-8000 capacitor bank control installation and operation instructions
MN916001EN—October 2018
Eaton.com
Approved sensor manufacturers
The CBC-8000 control supports measurements from both
line post and neutral current sensors.
The sensor inputs for the control are rated for 0 to 10 VAC.
Note:
If you are using a sensor that is not on the approved
list, refer to the
Communications Point Data Base
(TD916002EN)
for proper impedance programming.
Line post sensor
Line post sensors provide the means to provide accurate and
reliable current measurements to the CBC-8000 control.
The following sensors have been tested for use with the
control:
• Fisher Pierce Series 1301A
• Lindsey Multicore Sensor
Neutral current sensor
The optional CBC-NCSENSOR-35 and CBC-NCSENSOR8P-
35 current transducers by Eaton’s Cooper Power series are
designed for indoor and outdoor use. All components are
waterproof, including the core material and drain holes are
provided in the housing.
The CBC-NCSENSOR8P-35 offers a neutral current sensor,
wiring harness and 8-pin DIN connector. This assembly is
connected to the control with the 8-pin DIN connector that is
described in
8-Pin DIN connector (sensor inputs only) on
.
The CBC-NCSENSOR-35 sensor comes with a 35 foot
twisted-pair 18 AWG cable with pigtails. The cable may be
connected to the neutral current input of a junction box, or
routed to the meter base for socket mount controls.
Figure 42. CBC-NCSENSOR-35 neutral current sensor.
Table 9. Neutral current sensor specifications.
Spec
Value
Size
3.8” W x 3.3” H x 1” D, 1.25" window
(9.65 cm W x 8.38 cm H x 2.54 cm D, 3.18 cm window)
Current Range
50 A ±1% over the range of 0.5 A to 50 A calibrated to
0.5% full
Over Current
100 A continuously will not harm the CT – no DC
allowed
Voltage Range
600 VAC tested using 2500 VAC for up to 1 minute
Bandwidth
10 Hz to 5000 Hz
Output Voltage
10 VAC at 100 A input
Output Limiting
Set by internal resistor and windings – will saturate
without harm
Phase Displacement
Approximately 1 degree leading or lagging the input
current
Power Factor
Any load current power factor from 0.5 to 1.0 lead or lag
Temperature Range
-50° F to 185° F (-46° C to 85° C)
Temperature
Response
Less than 0.05% from -4° F to 185° F
(-20° C to 85° C)
Input Sensor Ratio
10:1