CBC-8000 capacitor bank control description
Description
The CBC-8000 control includes extensive system control
functionality, including time, temperature, current, voltage,
var and sensor control operational strategies. Other standard
features include, manual, automatic and remote modes,
safety delay timers, control security and neutral current
sensing with lockout.
The CBC-8000 control is designed for use with switched
distribution feeder capacitor racks and pad mount capacitors.
The metering functions of the control include instantaneous
current on a per-phase basis, instantaneous voltage and
power factor on a per-phase basis, and power (real, reactive,
apparent) on a per phase or total basis. The CBC-8000 control
also monitors Total Harmonic Distortion (THD) and odd
harmonics for voltage and current from the 3rd to the 13th
harmonic.
The front panel LCD display is used to configure the
operating settings for the control. It is also used to display
alarms, counter information, metering, and parameters.
Parameters can also be programmed via a personal
computer connected to the control through the front panel
USB port. Programming, interrogation, and operations are
performed with the ProView NXG software installed on a
computer.
The ProView NXG software includes additional functions
used to display configurable sequence of events, alarms, and
selectable communication points.
The input voltage of the control is auto-ranging from 85 to
265 VAC and it operates on both 50 and 60 Hz systems.
Serial number and date code location
The serial number and date of manufacture for the control is
printed on a label that is attached to the front panel as shown
in Figure 1. Refer to this date code for any warranty
questions. The date code is shown under the control serial
number and it states the week and year that the control was
manufactured.
Two additional labels are also provided for your use. The
labels are affixed to the inside of the front cover, above the
document holder.
Figure 1. CBC-8000 control serial number and date code.
Enclosure features
CBC-8000 controls manufactured after October 2016
(e.g., type 3) include the following additions:
• Door sensor
• Door latch
• Door hold
• Jaws meter base
• Ground lug
• Cable security sleeve
You can easily identify the type of control that you have by
entering function code 61 on the front panel and scrolling to
the Hardware ID. You can also view the control type with the
ProView NXG software by clicking
Help
About ProView
NXG
. The control types are as follows:
Type 1
– The control is a legacy control that does
not
con-
tain the door sensor or the new board with the RTC bat-
tery.
Type 2
– The control contains the new board with the RTC
battery, but it does not contain the door sensor. The con-
trol contains a new circuit board installed in the old legacy
cabinet.
Type 3
– The control contain the new board with the Real
Time Clock (RTC) battery and the new cabinet with the
door sensor.
Door sensor
A door sensor provides SCADA notification and timestamps
each time the control door is opened and closed. The
physical door contact, wiring and circuitry are all securely
contained inside the enclosure to prevent tampering.
Control
Serial
Number
Control
Date
Code
Содержание COOPER POWER SERIES