background image

2

Instruction Leaflet 

IL019226EN

Effective October 2018

C-HRG technical information  

and adjustment procedure 

  

EATON

 www.eaton.com

Receiving, handling, and storage

 CAUTION

TALL, NARROW STRUCTURE—MAY TIP OVER IF MISHANDLED. MAY 

CAUSE BODILY INJURY OR EQUIPMENT DAMAGE. DO NOT REMOVE 

FROM SKID UNTIL READY TO SECURE IN PLACE. READ HANDLING 

INSTRUCTIONS BELOW BEFORE MOVING.

Configurations

• 

Freestanding, single enclosure (NEMA Type 1, NEMA Type 3R)

• 

Wall-mounted control enclosure with separate wall-mounted 

resistor enclosure (both NEMA Type 1)

• 

Incorporated into a switchboard or switchgear assembly

Shipping weights:

• 

Freestanding: 650 lb (294.84 kg)

• 

Wall-mounted: 250 lb (113.4 kg), control assembly

• 

75 lb (34.02 kg), resistor assembly

Packing method:
Plastic overwrapped, suitable for standard truck transportation and 

indoor storage (all). Freestanding is bolted to fork-liftable skid. Skid 

adds approximately 4.00 inches (101.6 mm) to overall height.

Lifting

Unit may be lifted by the top-mounted lifting angles or moved into 

place with a forklift. The unit is a tall, narrow enclosure that can 

be tipped over if mishandled. For additional stability, keep it on its 

shipping skid until it is moved into place.
Unit may be rolled by placing pipes under the longitudinal skid 

members in at least four places, evenly spaced. As one pipe comes 

free, replace it ahead of the unit. Keep at least three evenly spaced 

pipes under the unit at all times.
Once the unit is in place, remove and discard the lifting angles. 

Replace the hardware to plug the exposed holes.

Storage

Choose a location that is suitable for indoor-type electrical 

equipment. (Note: treat a NEMA 3R unit as if it were indoor-type 

equipment until it is to be energized.) If the location is unheated, do 

not allow condensing humidity on or within the equipment. Provide 

sufficient heat and moving air to prevent condensation. Once the 

unit is energized, it will provide the required heat internally.

Installation

Unpacking

Remove plastic overwrap. Inspect for shipping damage. Report 

any damage immediately to the carrier and be sure to save the 

packing materials until inspected by the carrier. Inspect cover 

and compartment-mounted devices for blocking or other packing 

materials. Place all documents in the document pocket.

Equipment location

Observe all the appropriate codes with respect to clearances on 

all sides. This equipment is front accessible, meaning that side 

access is not required for installation and maintenance. When 

choosing the location for a separately mounted resistor assembly, 

keep in mind that it will give off considerable heat. Do not mount it 

on a combustible surface or adjacent to heat-sensitive material or 

equipment. 
Walls or floor must be sufficiently level to allow doors and covers to 

remain properly aligned with the structure. If embedded channel-iron 

floor sills are used, they must be at or above floor level.

Refer to assembly drawings provided with the unit for bolt-down 

hole locations. Bolt directly to wall or floor or channel-iron floor  

sills. Use 1/2-inch or 3/8-inch bolts for freestanding units and  

3/8-inch bolts for wall-mounted units. If floor sills are used, unit  

can be welded to channels. Use sufficient weld bead to approximate 

the strength of one 3/8-inch SAE grade 5 bolt at each corner.

Seismic 

If unit is furnished for suitable use in a seismic zone, refer to seismic 

installation guidelines referenced on the assembly drawing provided 

with the unit. Seismic installations supersede all other instructions. 

Wiring 

SAFETY PRECAUTIONS:
ONLY PERSONS TRAINED AND EXPERIENCED IN THE 

SERVICING OF ELECTRICAL DISTRIBUTION EQUIPMENT 

SHOULD ATTEMPT TO  SERVICE THIS  EQUIPMENT.

 

DANGER

HIGH VOLTAGE! 

WILL CAUSE DEATH, BODILY INJURY, OR EQUIPMENT DAMAGE. 

TURN OFF POWER AT THE SOURCE BEFORE WORKING INSIDE.

Use the schematic provided with the unit to determine the wiring 

interconnections required. All wiring must be in conformance  

with the NEC

T

 and/or local codes. Minimum wire sizes required  

are indicated on the schematic and must conform to the  

following minimum guidelines (based on 75 °C copper, per  

2011 NEC Table 310.15(B)(16)):

• 

Neutral: 8 AWG

• 

Ground: 8 AWG

• 

Phases: 12 AWG

Terminal block wire ranges:

• 

Neutral: #8

• 

Ground: #8 to 500 kcmil

• 

Phases: #12 to #8

• 

Control: #22 to #8 

Alarm contact ratings:

• 

600 Vac (A600)  10 A continuous 

 

 

7200 VA make / 720 VA break

• 

250 Vdc (P300)  5 A continuous  

 

 

1.1 A at 125 Vdc make/break 

 

 

0.55 A at 250 Vdc make/break

Final inspection and test log

• 

Turn all disconnects off. Perform any testing as directed by others

• 

Inspect for loose or missing connections

• 

Inspect all compartments for debris, tools, and so on 

• 

Replace all covers removed during installation

• 

Energize when directed to do so, and make all adjustments (refer 

to “Adjustment Procedure” section of this instruction manual) 

Using the test log provided (

Figure 12

) or a similar format of your 

choosing, test the unit and make the first entries. A document 

pocket is provided on the back of the control compartment door. 

Leave the test log (or a copy of it), a copy of the drawings, and a 

copy of this instruction manual in the pocket. Store the optional 

clamp-on ammeter in a clean, dry place. Do not store it in the control 

or resistor compartment.

Содержание C-HRG

Страница 1: ... PROCEDURES DESCRIBED IN THIS INSTRUCTION LEAFLET COULD RESULT IN DEATH BODILY INJURY OR PROPERTY DAMAGE CAUTION SPECIFIC OPERATING PROCEDURES MUST BE DEVELOPED BY THE RESPONSIBLE PARTY BECAUSE OF THE UNIQUE APPLICATION AND VAST VARIETY OF SYSTEM AND USER REQUIREMENTS FAILURE TO DEVELOP SPECIFIC PROCEDURES COULD LEAD TO IMPROPER USE OR OTHER MORE SERIOUS CONSEQUENCES C HRG equipment components and...

Страница 2: ...or a separately mounted resistor assembly keep in mind that it will give off considerable heat Do not mount it on a combustible surface or adjacent to heat sensitive material or equipment Walls or floor must be sufficiently level to allow doors and covers to remain properly aligned with the structure If embedded channel iron floor sills are used they must be at or above floor level Refer to assemb...

Страница 3: ...he current This is normal and comes from residual process oils and the curing of the resistor tube insulation Lower current levels may allow the initial burn off to occur gradually with little or no visible smoking Smoking may reoccur after the initial burn off if dust or other contamination is allowed to accumulate Refer to maintenance procedures outlined in this manual Current relay device 51N T...

Страница 4: ... through the resistor causing ground current to flow The system then reacts as it would under actual system ground conditions The lights turn on alarm contacts transfer and the optional alarm horn sounds Because periodic testing is the only assurance of continuing reliability a program of regular testing and maintenance is strongly recommended Pulser circuit The pulser circuit offers a convenient ...

Страница 5: ...o change in the pulsing current is noted along the entire length of a conduit then the fault may be in the connected load If the load is a panelboard distribution switchboard or motor control center repeat the process of checking all outgoing cable groups and conduits to find the faulted feeder If the fault is not found in an outgoing feeder the fault may be internal to that equipment An important...

Страница 6: ...o allow application on power systems with an available fault current of 200 kA rms at 600 Vac maximum If any fuse must be replaced be certain that only an identically rated ULT listed fuse is installed If a substandard or underrated fuse is used it may rupture violently causing burns electrical shock and or substantial equipment damage If the original fuse is not available or its markings not legi...

Страница 7: ... 141 IEEE Recommended Practice for Electrical Power Distribution for Industrial Plants recommends a resistance value that limits the maximum ground current between 5 A and 10 A for high resistance ground systems It also recommends for high resistance grounding to be used only in systems of 5 kV or lower charging currents of 5 5 A or lower and never in 15 kV systems A way to estimate the capacitive...

Страница 8: ...ent 5 Put the C HRG in test mode 6 Make sure the selector switch is held in test position The switch has a spring return to normal position and must be held in test position 7 The relay should not pick up the test current 8 De energize the equipment 9 Set the relay to one setting below the allowed ground return current 10 Re energize the equipment 11 Put the C HRG in test mode and hold the switch ...

Страница 9: ...019226EN Effective October 2018 C HRG technical information and adjustment procedure EATON www eaton com Figure 4 Four wire system fault detection via current relay Figure 5 Four wire system fault detection via voltmeter relay ...

Страница 10: ...g zag grounding transformers fault detection via current relay Figure 7 Three wire system zig zag grounding transformers fault detection via voltmeter relay Figure 8 Three wire system wye broken delta grounding transformers fault detection via current relay Figure 9 Three wire system wye broken delta grounding transformers fault detection via voltmeter relay ...

Страница 11: ...ion Leaflet IL019226EN Effective October 2018 C HRG technical information and adjustment procedure EATON www eaton com Figure 10 Typical enclosure dimensions for NEMA 1 free standing system dimensions in inches mm ...

Страница 12: ...ion Leaflet IL019226EN Effective October 2018 C HRG technical information and adjustment procedure EATON www eaton com Figure 11 Typical enclosure dimensions for NEMA 1 wall mounted system dimensions in inches mm ...

Страница 13: ...13 Instruction Leaflet IL019226EN Effective October 2018 C HRG technical information and adjustment procedure EATON www eaton com Figure 12 Test log ...

Страница 14: ...ction Leaflet IL019226EN Effective October 2018 C HRG technical information and adjustment procedure EATON www eaton com Figure 13 Standard front control panel detail voltmeter relay and alarm horn options shown ...

Страница 15: ...d adjustment procedure EATON www eaton com Figure 14 Typical control scheme with fault detection via current relay and alarm option with re alarm timer Figure 15 Typical control scheme with fault detection via voltmeter optional loss of control power relay and optional push to test lights ...

Страница 16: ... clamp on ammeter to trace fault always include all three phases within ammeter jaws Figure 16 Clamp on ammeter Note 3W load one cable per phase phase C is faulted to ground inside conduit Ground current can divide into several components depending on number conductivity and location of conduit ground points Figure 17 Example of a typical fault ...

Страница 17: ...ion and adjustment procedure EATON www eaton com Note 3W load one cable per phase phase C is faulted to ground inside conduit Ground current can divide into several components depending on number conductivity and location of conduit ground points Figure 18 Example of a typical fault ...

Страница 18: ...18 Instruction Leaflet IL019226EN Effective October 2018 C HRG technical information and adjustment procedure EATON www eaton com C HRG maintenance form Date Maintenance item By ...

Страница 19: ...19 Instruction Leaflet IL019226EN Effective October 2018 C HRG technical information and adjustment procedure EATON www eaton com ...

Страница 20: ... All Rights Reserved Printed in USA Publication No IL019226EN Z21760 October 2018 Eaton is a registered trademark All other trademarks are property of their respective owners C HRG technical information and adjustment procedure Instruction Leaflet IL019226EN Effective October 2018 ...

Отзывы: