O&M Manual for 40-1200A (480/600 Vac) ATC-900 3-Position, 

Open/Closed Transition Contactor Based Transfer Switch

1.2 General Information

Transfer switches are used to protect critical electrical loads 

against loss of power.  The load’s Source 1 power source is 

backed up by a Source 2 power source.  A transfer switch is 

connected to both the Source 1 and Source 2 power sources and 

supplies the load with power from one of the two sources.  In the 

event that power is lost from Source 1, the transfer switch trans-

fers the load to the Source 2 power source.  This transfer is auto-

matic.  Once Source 1 power is restored, the load is 

automatically transferred back to the Source 1 power source 

(Figure 2).

S

ource 1

S

ource 2

Lo

a

d

Figure 2. Typical Load Transfer Switch Schematic (Contactor 

Type).

In ATS equipment, the switch’s intelligence system initiates the 

transfer when the Source 1 power fails, falls below, or rises 

above a preset voltage.  If the Source 2 power source is a 

standby generator, the ATS initiates generator startup and trans-

fers to the Source 2 power source when sufficient generator 

voltage is available.  When Source 1 power is restored, the ATS 

automatically transfers back and initiates generator shutdown.  

In the event the Source 1 power source fails and the Source 2 

power source does not appear, the ATS remains connected to 

the Source 1 power source until the Source 2 power source does 

appear.  Conversely, if connected to the Source 2 power source 

and the Source 2 power source fails while the Source 1 power 

source is still unavailable, the ATS remains connected to the 

Source 2 power source.

ATSs automatically perform the transfer function and include 

three basic elements:

1. A power contactor to connect and disconnect the load to 

and from either power source.

2. Solenoids to make the transfer of the main contacts from 

source to source.

3. Intelligence/supervisory circuits to constantly monitor the 

condition of the power sources and thus provide the intelli-

gence necessary for the switch and related circuit operation.

1.2.1 Design Configuration

The Eaton contactor based ATS is a compact design that uses a 

power contactor to transfer essential loads from one power 

source to another (Figure 3 

[

1200A

])

.

LOGIC
PANEL

POWER
PANEL

VOLTAGE SELECTION

& TRANSFORMER PANEL

Figure 3. Typical 1200A Open Transition ATS.

The Eaton contactor based ATS is designed with easy installation 

and simplified maintenance in mind.  Three main panels comprise 

the contactor based ATS design:

 1. Power panel;

 2. Voltage selection and transformer panel; and 

 3. Microprocessor-based logic panel.

Содержание ATC-900

Страница 1: ...sition Contactor Based Transfer Switch Instruction Booklet Description Page Introduction 2 Receiving Handling and Storage 6 Equipment Description 7 Installation and Wiring 14 Operation 20 Testing and...

Страница 2: ...A It is provided as a guide for authorized and qualified person nel only Please refer to the specific WARNING and CAUTION in Section 1 1 2 before proceeding If further information is required by the p...

Страница 3: ...stored the ATS automatically transfers back and initiates generator shutdown In the event the Source 1 power source fails and the Source 2 power source does not appear the ATS remains connected to the...

Страница 4: ...ent catalog numbers provide a significant amount of relevant information that pertains to a particular piece of equipment The Catalog Number Identification Table Table 2 provides the required interpre...

Страница 5: ...applica ble setpoint ranges for the nominal voltage and frequency setting Source 2 Failed or Fails Source 2 is defined as failed when it is outside of its under voltage overvoltage underfrequency over...

Страница 6: ...o sure Care should be exercised however to protect the equip ment from impact at all times Do not remove the protective packaging until the equipment is ready for installation When the ATS equipment r...

Страница 7: ...POWER PANEL VOLTAGE SELECTION TRANSFORMER PANEL Figure 5A Three Basic Panels of an Open Transition ATS 1200A LOGIC PANEL POWER PANEL VOLTAGE SELECTION TRANSFORMER PANEL Figure 5B Three Basic Panels of...

Страница 8: ...North American market voltage selection panel consists of multi tap transformers contained in a steel case mounted in the transfer switch enclosure Figure 7 The cover has two connec tors on it with th...

Страница 9: ...oller has an operating temperature of 20 to 70 C 4 to 158 F The controller circuit board is protected by an insulating confor mal coating The specifications under normal operating conditions are as fo...

Страница 10: ...hieves a transfer between sources with no power interruption Both sources must be synchronized in fre quency phase and voltage before the transfer is initiated In phase transition is a feature that wi...

Страница 11: ...ad condition after a transfer from the generator source has been made Count down timing begins when the transfer is completed In applica tions where two generators are selected the same cool off timer...

Страница 12: ...Control This feature displays status information of a remotely located ATC 900 controller The HMI type Remote Annunciator will seri ally communicate with the ATC 900 over the Modbus 485 or Ethernet u...

Страница 13: ...ton ATS equipment enclosed in any of the enclosures listed in Table 3 is listed for application by UL and ULC In addition Eaton ATSs are listed in File E38116 by Underwriters Laborato ries Inc under S...

Страница 14: ...supporting the weight of the enclosed ATS equipment For standard ATSs avoid locations that are moist hot or dusty However Eaton offers optional enclosure designs that can be used in special environmen...

Страница 15: ...1A Typical Mounting of the ATS to a Mounting Surface Open Transition ATS for Wall Mounting Step 5 Double check to ensure that all packing and shipping materials have been removed Step 6 If Seismic Uni...

Страница 16: ...tion Verify that the lugs supplied will accommodate the power cables being used Also verify that the cables comply with local electrical codes Standard ATS equipment as supplied from the factory will...

Страница 17: ...ment is installed and operating properly 4 6 Engine Start Connection The engine control contact connections are located on the logic panel of the ATS Connect the engine start wires to the red ter mina...

Страница 18: ...232 J14 CT Earth Controller Ground J8 USB Front Panel Memory Stick Interface J11 I O Module s SW1 Modbus Terminator Module J13 RS 422 Interface Source Load Interface Switch Position Contacts For more...

Страница 19: ...he cover has two connec tors on it with the one on the right being selectable depending on the voltage applied to S1 and S2 The transformer unit is eas ily removed by removing the two front screws and...

Страница 20: ...OURCE 2 IF A GENERATOR CONTROL SELECTOR SWITCH TO THE OFF POSITION BEFORE ATTEMPTING A MANUAL TRANS FER To manually operate 1 Disconnect all sources of power 2 Disconnect the J7 connector from the ATC...

Страница 21: ...s on Source 1 4 Simultaneously the engine cool down timer initiates the shut down of the engine driven generator 5 Transfer of the load back to the Source 1 power source is now complete Section 6 Test...

Страница 22: ...ded for a preset time after transfer to the Source 1 power source is com pleted 6 1 5 Alternate Tests 1 Alternate operational tests may be possible depending upon the options provided with any given A...

Страница 23: ...to go to Source 1 Step 4 Depress the TRIP button located on the operating mechanism of the contactor to bring the contactor to neutral trip position Step 5 Depress the SELECT button located on the ope...

Страница 24: ...the structure area for safety hazards or potential maintenance problems Inspect the area especially where switching device is installed for any safety hazards including personnel safety and fire hazar...

Страница 25: ...at 68C8282H02 40 1200A Domestic Switch 480VAC 600VAC 4 Pole Cat 68C8282H02 Power Panel Close Transition Does not include Contactor 40 1200A Domestic Switch 480AC 600VAC 2 Pole Cat 69D8080H01 40 1200A...

Страница 26: ...LY SUGGESTED THAT THE FULL INSTRUCTIONS BE FOLLOWED FOR ALL INSTALLATIONS SET UP AND TESTING Step 1 Mount the ATS on a flat rigid surface Figure 18A 18B Shim if necessary Figure 18A Mounting Details O...

Страница 27: ...TAGE SELECTION PANEL LOGIC PANEL GROUND CONNECTION IB140036EN For more information visit www eaton com Instruction Booklet Effective October 2014 Page 27 O M Manual for 40 1200A 480 600 Vac ATC 900 3...

Страница 28: ...TION PANEL LOGIC PANEL GROUND CONNECTION For more information visit www eaton com IB140036EN Instruction Booklet Page 28 Effective October 2014 O M Manual for 40 1200A 480 600 Vac ATC 900 3 Position O...

Страница 29: ...e proper wire size as listed by the generator set Genset manufacturer For the I O connections there are some switches that the Inputs are wired to a terminal block while others are not When they are n...

Страница 30: ...ource 1 contactor Momentarily energize K3 N Is Source 1 available yet Y Source 1 is powering the load TDN timer times out if Option 32A is enabled TDN timer times out if Option 32A is enabled Source 1...

Страница 31: ...ad TDN timer times out if Option 32A is enabled TDN timer times out if Option 32A is enabled Source 1 is powering the load N Is Source 1 available yet TDEN timer times out Y Open Source 2 contactor En...

Страница 32: ...ww eaton com IB140036EN Instruction Booklet Page 32 Effective October 2014 O M Manual for 40 1200A 480 600 Vac ATC 900 3 Position Open Closed Transition Contactor Based Transfer Switch Figure 22 Close...

Страница 33: ...N For more information visit www eaton com Instruction Booklet Effective October 2014 Page 33 O M Manual for 40 1200A 480 600 Vac ATC 900 3 Position Open Closed Transition Contactor Based Transfer Swi...

Страница 34: ...information visit www eaton com IB140036EN Instruction Booklet Page 34 Effective October 2014 O M Manual for 40 1200A 480 600 Vac ATC 900 3 Position Open Closed Transition Contactor Based Transfer Swi...

Страница 35: ...N For more information visit www eaton com Instruction Booklet Effective October 2014 Page 35 O M Manual for 40 1200A 480 600 Vac ATC 900 3 Position Open Closed Transition Contactor Based Transfer Swi...

Страница 36: ...OF TRADE ARE MADE REGARDING THE INFORMATION RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN In no event will Eaton be responsible to the purchaser or user in contract in tort including negligence st...

Отзывы: