Instructional Booklet

Page

14

Effective: March 2010

Instructions for Installation, Operation and Maintenance of the

Eaton ATC-600 Automatic Transfer Switch Controller

For more information visit: www.eaton.com

IB ATS-1005

3.4.6  Setpoints Display

This display indicates presently programmed setpoints. The set-

points can only be altered in the Program Mode. Keep it mind, if a 

feature was not originally ordered and programmed, it will not be 

displayed (Figure 

8

). Refer to Section 5 for details.

3.4.7  Help Display

This display presents moving English language messages, explana-

tions and prompts to assist the operator while in any of the three 

operational modes. When the Help Pushbutton is pressed and 

released a second time during the scrolling of a message, the mes-

sage is aborted.

Section 4:  Operation

4.1  General

This section specifically describes the operation and functional use 

of the ATC-600. It is divided into three main categories:

Automatic Mode

Test Mode

Programming Mode

The practical use of and operation within each specific category 

will be discussed. In this section it is assumed that prior sections 

were reviewed and that the operator has a basic understanding of 

the hardware. It is important that the operator have a good grasp 

of the functional use of the operator panel as covered in Section 

3. This will make movement within each category and between 

categories a simple task. This familiarity will quickly put the unsur-

passed capabilities of ATC-600 at the operator’s fingertips.

4.2 Automatic Mode

The Automatic Mode of ATC-600 provides for automatic transfer 

and re-transfer from source to source as dictated by the features 

supplied and their programmed setpoint values. It provides a sum-

mary of ATC-600’s intelligence and supervisory circuits which 

constantly monitor the condition of both normal and emergency 

power sources thus providing the required intelligence for transfer 

operations. These circuits, for example, automatically initiate an 

immediate transfer of power when power fails or voltage levels 

drop below a preset value. Exactly what ATC-600 will initiate in 

response to a given system condition depends upon the combina-

tion of standard and selected optional features. Refer to Para-

graphs 1.3 and 1.4 for ATC-600’s standard and optional features. 
When the preferred source is connected and the automatic trans-

fer switch is operating normally, the Automatic LED blinks green 

and no message appears in the display window. In the event of a 

power failure, the display automatically becomes active showing 

the status of timers relative to an alternate source transfer. Once 

the alternate source becomes available, the transfer is made con-

sistent with pre-programmed features. In a similar manner, trans-

fer back to the preferred source is made once the preferred source 

is again available. System conditions relative to the sources and 

the load are clearly indicated by the LED type mimic bus. 

4.3  Control Inputs

As described in Section 2, the rear access area provides for 

access to all input connections. Each control input provides 50 

volts at 10ma. Refer to Figure 

3

 for a graphical representation and 

position of all input connections.

NOTICE

IT IS IMPORTANT TO REMEMBER THAT ATC-600 CONTINUES TO 

PROVIDE PROGRAMMED PROTECTION AND AUTOMATIC OPERA-

TION NO MATTER WHICH MODE THE DEVICE IS IN AT THE TIME IT 

IS CALLED UPON TO OPERATE. 

NOTICE

REFER TO APPENDIX D FOR AN OVERALL VIEW OF ATC-600 OPER-

ATIONS IN THE FORM OF A MENU TREE.

Содержание ATC-600

Страница 1: ...Instructional Booklet Description Page 1 Introduction 2 2 Hardware Description 7 3 Operator Panel 11 4 Operation 14 5 Programming 19 6 Troubleshooting and Maintenance 22 Appendix A Status Display Mes...

Страница 2: ...onse quential damage or loss whatsoever including but not limited to damage or loss of use of equipment plant or power system cost of capital loss of power additional expenses in the use of existing p...

Страница 3: ...es from most system voltages available worldwide at 50 or 60 Hertz In addition a period of no control power operation is provided ATC 600 moni tors the condition of the 3 phase line to line voltage an...

Страница 4: ...o permit sta bilization of the Emergency power source before the transfer is made This timer will begin the countdown from its setting value when the Emergency Source becomes available If the Normal S...

Страница 5: ...1 for an overvoltage con dition When the Source 1 voltage rises to a value equal to or above the overvoltage dropout setting the source will become unavailable The source s voltage will then have to d...

Страница 6: ...the load is transferred in either direction to prevent excessive in rush currents due to out of phase switching of large motor loads This feature is not available with the Neutral Load Sense Delay TDN...

Страница 7: ...ng the function of specific pushbuttons 2 3 Rear Access Area The rear access area of the ATC 600 is normally accessible from the rear of an open panel door Figure 2 All wiring connections to the ATC 6...

Страница 8: ...5 Display LEDs seven LEDs to identify the Display Win dow Information 6 Help Pushbutton provides English language help information in any operational mode 7 Increase Decrease Pushbuttons used individu...

Страница 9: ...the ATC 600 is always supplied with a communications port a PONI can be easily retrofitted to the ATC 600 at any time It is recom mended that the control power to the ATC 600 be removed prior to conne...

Страница 10: ...ncy Measurement Range 40 to 80 Hz Frequency Measurement Accuracy 0 1 Hz Undervoltage Dropout Range Volts Breaker Switch Style ATS 50 to 97 of Nominal System Voltage Undervoltage Pickup Range Volts Bre...

Страница 11: ...e 1 is the preferred source choice Source 1 Connected Status LED This LED is lit green if Source 1 is connected This is accom plished by sensing the Source 1 breaker via the S1 closed auxil iary conta...

Страница 12: ...ll occur and the engine will run for the programmed run time 3 3 4 Display Select Pushbutton As the Display Select Pushbutton is pressed and released ATC 600 steps through the following display catego...

Страница 13: ...itions will be shown OVER V The source has risen above the dropout setting and not dropped below the pickup setting UNDER V The source has dropped below the dropout setting and not risen above the pic...

Страница 14: ...y the features supplied and their programmed setpoint values It provides a sum mary of ATC 600 s intelligence and supervisory circuits which constantly monitor the condition of both normal and emergen...

Страница 15: ...contact will activate the Emergency Inhibit input If the Emergency Inhibit contact is opened when the load is con nected to the Normal Source no action will be taken if the Normal Source is available...

Страница 16: ...able Relay II s are used to enable up to 10 separate loads The Addressable Relay II must be set for 1200 BAUD rate WATCHDOG feature disabled RELAY PULSE feature disabled Address range from 002 to 00B...

Страница 17: ...include improper circuit breaker operation motor operator failure and unsuccessful closed or in phase transition An alarm may be reset by simultaneously press ing the Increase and Decrease Pushbuttons...

Страница 18: ...E countdown the Emergency Source goes unavailable more than three times Each time TDNE will restart 4 If the Emergency Source is powering the load and it goes unavailable for more than the TDEF settin...

Страница 19: ...rt Users can reprogram setpoints as well as other parameters The time and date can be changed while the device is in either the Run Mode or the Program Mode Setpoints however can only be changed while...

Страница 20: ...s 2OVD Source 2 Overvoltage Dropout Volts 105 to 120 1 115 Volts 1OVP Source 1 Overvoltage Pickup Volts 103 to Dropout 2 1 110 Volts 2OVP Source 2 Overvoltage Pickup Volts 103 to Dropout 2 1 110 Volts...

Страница 21: ...Note 3 Set to order specific value Table 2 Programmable Features Setpoints Cont PROGRAMMABLE FEATURE DISPLAY DISPLAY EXPLANATION SETPOINT POSSIBILITIES FACTORY DEFAULT VALUE MEASURE PHASE Number of S...

Страница 22: ...ncy setpoints Re adjust all dropout and pickup setpoints to default values Changed undervoltage or overvoltage or underfre quency or overfrequency dropout setpoint and the pickup setpoint changed also...

Страница 23: ...crease push buttons simultaneously to clear message Check Source 2 circuit breaker spring release SR wiring Press Increase and Decrease push buttons simultaneously to clear message Check S2 Aux Close...

Страница 24: ...plug is in the proper posi tion to match the system voltage Step 4 Look for any obviously burned components Determine the cause and rectify if possible Replace defective com ponents after the cause is...

Страница 25: ...rect line voltage and frequency available at terminals E1 E2 and E3 Record the readings If YES Proceed to Step 3 If NO Verify that there is output voltage from the generator Step 3 Is the voltage sele...

Страница 26: ...00 are de energized These may also be present on some of the terminal blocks Step 3 Before disconnecting any wires from the unit make sure they are individually identified to assure that reconnec tion...

Страница 27: ...ngine test sequence press Engine Test pushbutton again or press Increase and Decrease simultaneously to clear WAIT Waiting for the generator source voltage and frequency to become available TDNV Waiti...

Страница 28: ...2 Connected Time This counter logs time in hours whenever Source 2 is connected to the load Time will start being logged at the time the S2 AUX control input is closed This counter will count up to 99...

Страница 29: ...7 Engine test 8 Manual re transfer 9 Engine Test via communications 10 Go to neutral 11 Program mode 12 Options or setpoints error 13 Emergency Inhibit 14 Go to Emergency 15 Lock out 16 Failed to sync...

Страница 30: ...l over between AM and PM values Minutes By using the Increase or Decrease Pushbuttons the minutes of the day can be adjusted to the present value The number will continuously roll over between 0 and 5...

Страница 31: ...Phase Sensing with Open Transition FREQ Condition STEP STEP STEP STEP STEP STEP STEP STEP STEP STEP STEP STEP STEP STEP STEP STEP Display is blank or a status message appears Note All menu items are n...

Страница 32: ...RY TIME DATE SET POINTS TDES TDNE TDEN TDEC NOMF NOMV 1UVD 2UVD 1UVP 2UVP 1OVD 2OVD 1OVP 2OVP 1UFD 2UFD 1UFP 2UFP 1OFD 2OFD 1OFP 2OFP TDN TDNLD LDCY PRF SRC EXER EXLD PEDAY PEH PEMIN MANTR CTDNE TMODE...

Страница 33: ...K3 Source 1 becomes unavailable or Engine Test Plant Exerciser Go To Emergency TDES timer times out Send Engine Start signal Energize Gen Start relay TDNE timer times out Open Source 1 breaker Energi...

Страница 34: ...omentarily energize K3 Source 1 becomes unavailable or Go To Emergency TDNE timer times out Open Source 1 breaker Energize K2 Y Source 2 is powering the load Close Source 1 breaker Momentarily energiz...

Страница 35: ...ource 2 Engine Test Plant Exerciser Go To Emergency TDES timer times out Send engine start signal Energize Gen Start relay TDNE timer times out Y Source 2 is powering the load Energize Alarm relay Ope...

Страница 36: ...OR USAGE OF TRADE ARE MADE REGARDING THE INFORMATION RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN In no event will Eaton be responsible to the purchaser or user in contract in tort including neg...

Отзывы: