Instructional Booklet
Page
20
Effective: March 2010
Instructions for Installation, Operation and Maintenance of the
Eaton ATC-600 Automatic Transfer Switch Controller
For more information visit: www.eaton.com
IB ATS-1005
5.4 Programmable Features/Setpoints
All ATC-600 programmable features and associated setpoint pos-
sibilities with any required explanations are presented in Table
2
.
Remember, only features originally ordered and factory pro-
grammed will appear in the display.
Table 2. Programmable Features/Setpoints.
CAUTION
CHANGING THE SYSTEM NOMINAL VOLTAGE OR FREQUENCY SET-
POINTS WILL AUTOMATICALLY CHANGE ALL THE PICKUP AND
DROPOUT SETTINGS TO NEW DEFAULT VALUES.
PROGRAMMABLE
FEATURE DISPLAY
DISPLAY
EXPLANATION
SETPOINT
RANGE
FACTORY DEFAULT
VALUE
MEASURE
TDES
Time Delay Engine Start Timer
0 to 120 Seconds
0:03
Minutes: Seconds
TDNE
Time Delay Normal to Emergency Timer
0 to 1800 Seconds
0:00
Minutes: Seconds
TDEN
Time Delay Emergency to Normal Timer
0 to 1800 Seconds
5:00
Minutes: Seconds
TDEC
Time Delay Engine Cool Down Timer
0 to 1800 Seconds
5:00
Minutes: Seconds
NOMF
System Nominal Frequency (Hertz)
50 or 60 Hz
3
60
Hertz
NOMV
System Nominal Voltage (Volts)
120 to 600 Volts
3
120
Volts
1UVD
Source 1 Undervoltage Dropout (Volts)
97 to 50% of Nominal
1
80%
Volts
2UVD
Source 2 Undervoltage Dropout (Volts)
97 to 50% of Nominal
1
80%
Volts
1UVP
Source 1 Undervoltage Pickup (Volts)
(D2%) to 99%
1
90%
Volts
2UVP
Source 2 Undervoltage Pickup (Volts)
(D2%) to 99%
1
90%
Volts
1OVD
Source 1 Overvoltage Dropout (Volts)
105 to 120%
1
115%
Volts
2OVD
Source 2 Overvoltage Dropout (Volts)
105 to 120%
1
115%
Volts
1OVP
Source 1 Overvoltage Pickup (Volts)
103% to (Dropout-2%)
1
110%
Volts
2OVP
Source 2 Overvoltage Pickup (Volts)
103% to (Dropout-2%)
1
110%
Volts
1UFD
Source 1 Underfrequency Dropout (Hertz)
90 to 97%
2
94%
Hertz
2UFD
Source 2 Underfrequency Dropout (Hertz)
90 to 97%
2
94%
Hertz
1UFP
Source 1 Underfrequency Pickup (Hertz)
(D1 Hz) to 99%
2
96%
Hertz
2UFP
Source 2 Underfrequency Pickup (Hertz)
(D1 Hz) to 99%
2
96%
Hertz
1OFD
Source 1 Overfrequency Dropout (Hertz)
103 to 110%
2
106%
Hertz
2OFD
Source 2 Overfrequency Dropout (Hertz)
103 to 110%
2
106%
Hertz
1OFP
Source 1 Overfrequency Pickup (Hertz)
101% to (Dropout -1 Hz)
2
104%
Hertz
2OFP
Source 2 Overfrequency Pickup (Hertz)
101% to (Dropout -1 Hz)
2
104%
Hertz
TDN
Time Delay Neutral Timer
0 to 120 Seconds
0:00
Minutes: Seconds
TDNLD
Time Delay Neutral Load Decay
0 = Disabled
1 = Enabled
1
-
LDCY
Load Decay Voltage
2 to 30% of Nominal Voltage
30
Volts
PRF SRC
Preferred Source
None
1=Source 1
2=Source 2
1
-
EXER
Plant Exerciser Enabled or Disabled
1=Enabled
0= Disabled
1
-
EXLD
Load Transfer with Plant Exerciser
1=Enabled
0= Disabled
1
-
PEDAY
Plant Exerciser Day of Week
1 to 7
(1= Sunday)
1
Week Day
PEH
Plant Exerciser Hour
1 am to 11 pm
1 AM
Hour
PREMIN
Plant Exerciser Minute
0 to 59 Minutes
0
Minutes
MANTR
Re-Transfer Mode
0= Automatic
1= PB Return
0
-
CTDNE
Commitment to Transfer in TDNE
0= Not Committed
1= Committed
0
-
TMODE
Engine Test With/Without Load Transfer
0= No Load Transfer
1= Load Transfer
2= Disable Test Pushbutton
1
-
TER
Engine Test/Plant Exerciser Run Time
0 to 600 Minutes
0:30
Hours: Minutes
TPRE
Pre-Transfer Sub-Network
Time Delay
1 to 300 Seconds
0:01
Minutes: Seconds
GENNO
Number of Generators
(Single Generator Must Be On Source 2)
0 to 2
1
-