The setpoints on each ATC-300+ needs to be set as follows: 

 
Baud Rate:    9600 

 

Address: 

 01, 02, 03, and 04 (different address for each ATC-300+) 

 

Terminated:   On (termination micro-switch on back side of the last ATC-300+) 

 
There is a system menu on the HMI that allows the operator to change items like 
touch screen force, touch screen calibration, time & date, brightness & contrast, alarm 
and touch volume, and others.  The HMI should be set up so the user will not have to 
adjust anything in the field.  If a change is desired, there are two ways of 
accomplishing this:  
 
The first is to simply press the small SYSTEM button on the back of the unit for two 
seconds.  The system menu will now be displayed on the screen.  The menus are self-
explanatory but if help is required, one can download the manual from the Eaton 
website under “HMiSoft User Manual” effective February 2011.  After the adjustments 
have been made, simply push the SYS button again for two seconds. Also see the 
instruction leaflet IL04801003E that came with the display.   
 
The second option is to push the “SETUP” button and the new screen that appears 
will have a “SYSTEM SETUP” button.  This is useful if the back of the unit is not easily 
accessible.  This button will get the user in the same area as the SYSTEM button on 
the back of the unit. 
 

1.4 Screens 

 
There are six screens that are displayed for the ATS functionality.  Each screen has a 
return button to return to previous screen.  Each of the screens and the associated 
buttons are described below.  
 
 

Screens:                            

 

 

 

Top Level with ATS Select and System Setup

 

Содержание ATC-300+

Страница 1: ...terface with up to 4 Automatic Transfer Switches It not only displays the status of the switch it also provides several popular control functions The 7 Ethernet RAC Kit contains the following HMIVU07C...

Страница 2: ...t and should require no user programming Communication with the ATS controller is accomplished via Modbus RS 485 serial network to the gateway Drawing 66A8395E shows the wiring of the unit which inclu...

Страница 3: ...3 PXG 400E Gateway...

Страница 4: ...displayed on the screen The menus are self explanatory but if help is required one can download the manual from the Eaton website under HMiSoft User Manual effective February 2011 After the adjustment...

Страница 5: ...y controller press the setup button password protected level 3 To continue to the second level for any working controller simply press on its corresponding quadrant If the system switches to emergency...

Страница 6: ...d O or S2 back to S1 X To clear the information simply push the Clear History button ALARM Messages 1 Overvoltage 2 Undervoltage 3 Over Frequency 4 Under Frequency 5 Plant Exerciser 6 Engine Test 7 Re...

Страница 7: ...Passwords are needed to get to the Engine Test and Go to Emergency To S2 screens These two screens are at security level two which is factory set to AC44 If you would like to change any of the passwo...

Страница 8: ...he Go To S2 button the switch will transfer to source 2 if there is available power on S2 To go back to S1 push the Return to S1 button One can use the Bypass TDNE TDEN if desired The Manual Retransfe...

Страница 9: ...9 procedures include but are not limited to switch doors being closed and latched personnel knowledgeable of transfers and other site safety recommended procedures...