8
Engine Test
By pressing Start Test, the controller will start the generator and then run the engine
test when S2 is available. (Push the Silence Alarm button to remove the audio). To
abort the test before the time is up, push the Abort Test button. One can use the
Bypass TDNE/TDEN if desired.
Transfer Control
By pressing the Go To S2 button, the switch will transfer to source 2 if there is
available power on S2. To go back to S1, push the Return to S1 button. One can use
the Bypass TDNE/TDEN if desired. The Manual Retransfer button will appear if the
controller has manual retransferring enabled. Pressing it will send the command to
the ATC-300+ controller, but only if it is enabled.
CAUTION
This is a remote control device. Caution should be applied to make sure that
appropriate procedures are in place for Engine Tests and To S2. Appropriate