Instruction Booklet 

Effective:  January 2012

Page 

25

ATC-300+ Automatic 

Transfer Switch Controller

Table 3. Troubleshooting Guide (Cont.)

7.3  ATC-300+ Replacement

Follow these procedural steps to replace the ATC-300+.

Step 1: Turn off the control power at the main disconnect or iso-

lation switch of the control power supply.  If the switch 

is not located within view from the ATC-300+, lock it 

out to guard against other personnel accidentally turning 

it on.

Step 2: Verify that all “foreign” power sources wired to the 

ATC-300+ are de-energized.  These foreign power 

sources may also be present on some of the terminal 

blocks.

Step 3: Before disconnecting any wires from the unit, make sure 

they are individually identified to assure that reconnec-

tion can be correctly performed.  Make a sketch to help 

with the task of terminal and wire identification.

Step 4: Remove all wires and disconnect plug-type connectors.

Step 5: Remove the four (4) 3/8 inch nuts, located on the four 

corners, which hold the unit and trim plate against the 

door or panel.  These are accessed from the back of 

the unit.  

Step 6: Remove the unit from the door or panel.  Lay the original 

mounting screws aside for later use.

Step 7: Align the unit with the opening in the door or panel.

Step 8: Using the original mounting hardware, secure the 

replacement unit to the door or panel.

Step 9: Using the sketch mentioned in Step 3, replace each wire 

at the correct terminal and make sure each is secure.  

Make certain that each harness plug is securely seated.

Step 10:  Restore control power to the unit.

7.4  Maintenance and Care

The ATC-300+ is designed to be a self-contained and mainte-

nance-free unit.  The printed circuit boards are calibrated and con-

formally coated at the factory.  They are intended for service by 

factory-trained personnel only.

SYMPTOM

PROBABLE CAUSE

POSSIBLE SOLUTION(S)

Unit will not perform an Engine Test.

Engine Test pushbutton was not pressed.

Display is not displaying the Home screen before initiating the test.

Engine Test setpoint is set to Disable (Value of “2”).

Generator became unavailable when connected to the load.

Generator became unavailable before connecting to the load.

Generator voltage and/or frequency did not become available within 

90 seconds of engine starting.

Press the Engine Test pushbutton to initiate the test.

Use the Step/Enter pushbutton to step to the Home screen.  If a 

timer is timing down, wait until it is done.

Re-program the Engine Test setpoint.

Increase the Time Delay Emergency Fail (TDEF) timer setpoint.

Check the generator for proper function.

Verify the voltage and/or frequency with a multimeter.  Check 

the programmed setpoint values.  Check the engine mainte-

nance.

Plant Exerciser failed to exercise.

Incorrect date or time setting.

Incorrect setpoint programmed for the PE DAY, PE HOUR, and/or PE MIN-

UTE.
Generator voltage and/or frequency did not become available within 90 sec-

onds of engine starting.

Generator became unavailable when connected to the load.

Generator became unavailable before connecting to the load.

Verify real time clock settings for the time and date.

Re-program the PE DAY, PE HOUR, and/or PE MINUTE setpoint.

Verify the voltage and/or frequency with a multimeter.  Check 

the programmed setpoint values.  Check the engine mainte-

nance.

Increase the TDEF timer setpoint.

Check the generator for proper function.

Engine fails to start after the TDES times out.

Incorrect wiring.

Gen Start relay contacts are not closed.

Engine did not start.

Check the wiring between the Gen Start relay (J-5, Pins 13 and 

14) and the engine.

Replace the unit.

Check the generator for proper function.

 CAUTION

SUPPORT THE ATC-300+ FROM THE REAR WHEN THE SCREWS 

ARE LOOSENED OR REMOVED IN STEP 5.  WITHOUT SUCH SUP-

PORT, THE UNIT COULD FALL OR THE PANEL COULD BE DAM-

AGED.

Содержание ATC-300+

Страница 1: ...Typical Function of the ATC 300 Controller 13 Operation 15 Programming 20 Troubleshooting and Maintenance 24 Appendix A Display Messages for Status and Timers 26 Appendix B Operational Flowcharts 27 A...

Страница 2: ...TO INSURE THAT PERSONNEL ARE AL ERT TO WARNINGS WHICH APPEAR THROUGHOUT THE DOCUMENT IN ADDITION WARNINGS AND CAUTIONS ARE ALL UPPER CASE AND BOLDFACE COMPL ETELY READ AND UNDERSTAND THE MATERIAL PRE...

Страница 3: ...only available power source and also forces a transfer or re transfer operation to the only available power source Re Transfer Re transfer is defined as a change of the load connection from the Sourc...

Страница 4: ...generator to cool down by running unloaded Timing begins on completion of the re transfer cycle Adjustable 0 1800 Seconds 5 Source 2 Monitoring and Protection This feature provides monitoring and pro...

Страница 5: ...L ED that when lit indicates the load is connected to Source 1 12D Source 2 Source Connected This feature provides a red L ED that when lit indicates the load is connected to Source 2 Power Source Av...

Страница 6: ...ides standard or optional transfer modes mode selec tion devices and operational methods for ATSs 29J Type of Operation MANTR Operation new feature This feature provides for a seletion between an auto...

Страница 7: ...onnected 4 Source 2 Available 5 Source 2 Connected There are seven input functions accessible through the pushbut tons 1 Help Lamp Test 2 Engine Test 3 Step Enter 4 Increase 5 Decrease 6 Alarm Reset 7...

Страница 8: ...entarily illumi nate then the following information will scroll across the display Serial number of the ATC 300 Controller Hardware revision number parts list revision number Software version and revi...

Страница 9: ...when dis cussing the rear access area is with the panel door open and the User fac ing the back of the ATC 300 Controller Located at the left rear of the chassis are connectors J1 J2 and J7 J1 and J2...

Страница 10: ...Style ATS 103 to Dropout 2 of the Nominal System Voltage Underfrequency Dropout Range Breaker Switch Style ATS 90 to 97 of the Nominal System Frequency Underfrequency Pickup Range Breaker Switch Style...

Страница 11: ...g that the phase sequence is reversed 3 1 2 Time Date Display The Time Date Display indicates real time in terms of hours min utes and seconds and month day and year It also indicates individual time...

Страница 12: ...on to step to the TRANSFER HIS TORY message Press the Increase pushbutton to display the most recent transfer event T01 along with the type and cause of the event Press the Decrease pushbutton to disp...

Страница 13: ...will time down if pro grammed and if S1 is available Engine Test or Plant Exercise The K2 relay will energize The S1 connected input MUST open within 6 seconds see above K2 will open IF TDN is pro gr...

Страница 14: ...rmation visit www chfire com IM05805022K Instruction Booklet Page 14 Effective January 2012 ATC 300 Automatic Transfer Switch Controller Figure 4 Connectors on the ATC 300 Controller ATC 300 Controlle...

Страница 15: ...ler that the Source 2 device is closed When this input is in the Unconnected state it indicates to the ATC 300 that the Source 2 device is open This input is typically wired to the Source 2 device aux...

Страница 16: ...ntil the Emergency Inhibit input is de activated 5 5 Output Relay The primary control outputs of the ATC 300 Controller are dry relay contacts These relays are comprised of one latching Form A relay t...

Страница 17: ...IM05805022K For more information visit www chfire com Instruction Booklet Effective January 2012 Page 17 ATC 300 Automatic Transfer Switch Controller Figure 5 Connector Output Relay Connections...

Страница 18: ...in J 5 Pin 6 The pre transfer relay contacts are rated for 10 A 1 3 HP 250 Vac The DC rating is 10 A 30 Vdc 5 5 1 2 Transfer Operations Connections K1 K2 K3 and K4 are factory wired to operate the tra...

Страница 19: ...the Engine Test will be terminated An engine test may also be aborted in the following ways 1 If the Emergency Source does not become available within 90 seconds of the ATC 300 providing the engine st...

Страница 20: ...setpoints while in Program Mode WHILE IN THE PROGRAM MODE THE ATC 300 CONTROLLER IS NEVER OFF LINE AND CONTINUES TO FUNCTION IN ACCORDANCE WITH PREVIOUSLY PROGRAMMED SETPOINTS 6 2 Password To enter th...

Страница 21: ...s and their programmed values Each press of the Step Enter pushbutton will advance the program to the next setpoint Setpoint values CANNOT be changed while in the Display Only Mode 6 4 Change Setpoint...

Страница 22: ...Overvoltage Dropout Range Breaker Switch Style ATS 105 to 120 of Nominal System Voltage 115 S1 OV PICK Volts Source 1 Overvoltage Pickup Range Breaker Switch Style ATS 103 to Dropout 2 of Nominal Sys...

Страница 23: ...Timer 10 to 30 0 20 TDEF Seconds Time Delay Emergency Fail Timer 0 sec to 6 sec 6 SYNC TIME Minutes In phase Transition Synchronization Timer 1 min to 60 min 5 PHASE REV Phase Reversal OFF ABC or CBA...

Страница 24: ...ecifications Replace the unit One or more voltage phases read incorrectly Incorrect wiring ATC 300 is malfunctioning Verify voltage with multimeter Check wiring Replace the unit Verify ground connecti...

Страница 25: ...rvice by factory trained personnel only SYMPTOM PROBABLE CAUSE POSSIBLE SOLUTION S Unit will not perform an Engine Test Engine Test pushbutton was not pressed Display is not displaying the Home screen...

Страница 26: ...R S2 Waiting for the Source 2 source voltage and frequency to become available TD PRE TRAN Countdown timer while waiting for a pre transfer acknowledge input SOURCE 1 DEVICE Indicates that the Source...

Страница 27: ...lable or Engine Test Plant Exercise Go To Emergency TDES timer times out Send Engine Start signal Energize Gen Start relay Is Source 2 Available TDNE timer times out Sends pretransfer signal TPRE time...

Страница 28: ...ring the load Source 1 becomes unavailable or Go To Emergency Is Source 2 Available TDNE timer times out Sends pretransfer signal TPRE timer times out If Source 1 is Available Open Source 1 Energize K...

Страница 29: ...0 02 am Source 1 120 VAC 60Hz Source 2 120 VAC 60Hz S1 FREQ 60 0 S1 Vca 120 S1 Vbc 120 S1 Vab 120 SOURCE 1 GOOD S2 Vab 120 S2 Vbc 120 S2 Vca 120 S2 FREQ 60 0 SOURCE 2 GOOD TIME 10 01 02 AM A TRANSFER...

Страница 30: ...SWORD NEW PASSWORD 0000 Use Inc Dec TDNE 0 00 Use Inc Dec STEP STEP STEP STEP STEP YES STEP STEP STEP STEP STEP B TDES 0 03 Use Inc Dec STEP NEW PASSWORD 0000 Use Inc Dec NEW PASSWORD 0000 Use Inc Dec...

Страница 31: ...c Dec S1 UV PICK 187 Use Inc Dec C S1 OV PICK 228 Use Inc Dec STEP STEP STEP STEP STEP STEP STEP STEP STEP STEP S1 UF DROP 57 0 Use Inc Dec STEP STEP STEP STEP STEP STEP STEP STEP STEP B S2 OV PICK 22...

Страница 32: ...nc Dec PE MINUTE 0 Use Inc Dec TEST MODE 0 Use Inc Dec D VOLT UNBAL 1 Use Inc Dec STEP STEP STEP STEP STEP STEP STEP STEP STEP STEP UNBAL PICK 10 Use Inc Dec STEP STEP STEP STEP STEP STEP STEP STEP ST...

Страница 33: ...c YEAR 2012 Use Inc Dec STEP STEP STEP STEP STEP STEP STEP NO E RESET NO SYSTEM COUNTERS STEP ENGINE RUN 9999 PUSH Alarm Reset RESET NO ALL COUNTERS STEP YES STEP NO D MINUTES 2 Use Inc Dec WEEKDAY 4...

Страница 34: ...Page 34 Effective January 2012 ATC 300 Automatic Transfer Switch Controller S1 AVAIL 9999 PUSH Alarm Reset STEP STEP STEP SAVE YES SETPOINTS E S2 AVAIL 9999 PUSH Alarm Reset LOAD ENERG 9999 PUSH Alarm...

Страница 35: ...94 308 336 389 486 80 96 166 176 192 304 332 384 480 79 95 164 174 190 300 328 379 474 78 94 162 172 187 296 324 374 468 77 92 160 169 185 293 320 370 462 76 91 158 167 182 289 315 365 456 75 90 156 1...

Страница 36: ...47 684 113 136 235 249 271 429 469 542 678 112 134 233 246 269 426 465 538 672 111 133 231 244 266 422 461 533 666 110 132 229 242 264 418 457 528 660 Pickup Breaker 109 131 227 240 262 414 452 523 65...

Страница 37: ...IM05805022K For more information visit www chfire com Instruction Booklet Effective January 2012 Page 37 ATC 300 Automatic Transfer Switch Controller NOTES...

Страница 38: ...For more information visit www chfire com IM05805022K Instruction Booklet Page 38 Effective January 2012 ATC 300 Automatic Transfer Switch Controller NOTES...

Страница 39: ...IM05805022K For more information visit www chfire com Instruction Booklet Effective January 2012 Page 39 ATC 300 Automatic Transfer Switch Controller NOTES...

Страница 40: ...ATION RECOMMENDATIONS AND DESCRIPTIONS CON TAINED HEREIN In no event will EATON be responsible to the purchaser or user in contract in tort including negligence strict liability or otherwise for any s...

Отзывы: