ATC-300+ Automatic
Transfer Switch Controller
The following setpoints are programmable if the corresponding feature is programmed.
Table 2. Programmable Features and Setpoints
SETPOINT
SETPOINT UNITS
DESCRIPTION
RANGE
FACTORY
DEFAULT
New Password
Four Digits
Set New Password
0000 to 9999
0300
TDES
Minutes: Seconds
Time Delay Engine Start
0 to 120 seconds
0:03
TDNE
Minutes: Seconds
Time Delay Normal to Emergency
0 to 1800 seconds
0:00
TDEN
Minutes: Seconds
Time Delay Emergency to Normal
0 to 1800 seconds
5:00
TDEC
Minutes: Seconds
Time Delay Engine Cool-off
0 to 1800 seconds
0:00
NOM FREQ
Hertz
Nominal Frequency
50 or 60 Hz
As ordered
NOM VOLTS
Volts
Nominal Voltage
120 to 600 volts
As ordered
S1 UV DROP
Volts
Source 1 Undervoltage Dropout Range:
Breaker/Switch Style ATS
50 to 97% of Nominal System Voltage
85%
S2 UV DROP
Volts
Source 2 Undervoltage Dropout Range:
Breaker/Switch Style ATS
50 to 97% of Nominal System Voltage
85%
S1 UV PICK
Volts
Source 1 Undervoltage Pickup Range:
Breaker/Switch Style ATS
(D2%) to 99% of Nominal System Voltage
90%
S2 UV PICK
Volts
Source 2 Undervoltage Pickup Range:
Breaker/Switch Style ATS
(D2%) to 99% of Nominal System Voltage
90%
S1 OV DROP
Volts
Source 1 Overvoltage Dropout Range:
Breaker/Switch Style ATS
105 to 120% of Nominal System Voltage
115%
S2 OV DROP
Volts
Source 2 Overvoltage Dropout Range:
Breaker/Switch Style ATS
105 to 120% of Nominal System Voltage
115%
S1 OV PICK
Volts
Source 1 Overvoltage Pickup Range:
Breaker/Switch Style ATS
103% to (Dropout -2%) of Nominal System Voltage
110%
S2 OV PICK
Volts
Source 2 Overvoltage Pickup Range:
Breaker/Switch Style ATS
103% to (Dropout -2%) of Nominal System Voltage
110%
S1 UF DROP
Hertz
Source 1 Underfrequency Dropout Range:
Breaker/Switch Style ATS
90 to 97% of Nominal System Frequency
94%
S2 UF DROP
Hertz
Source 2 Underfrequency Dropout Range:
Breaker/Switch Style ATS
90 to 97% of Nominal System Frequency
94%
S1 UF PICK
Hertz
Source 1 Underfrequency Pickup Range:
Breaker/Switch Style ATS
(D1 Hz) to 99% of Nominal System Frequency
96%
S2 UF PICK
Hertz
Source 2 Underfrequency Pickup Range:
Breaker/Switch Style ATS
(D1 Hz) to 99% of Nominal System Frequency
96%
S1 OF DROP
Hertz
Source 1 Overfrequency Dropout Range:
Breaker/Switch Style ATS
103 to 110% of Nominal System Frequency
106%
S2 OF DROP
Hertz
Source 2 Overfrequency Dropout Range:
Breaker/Switch Style ATS
103 to 110% of Nominal System Frequency
106%
S1 OF PICK
Hertz
Source 1 Overfrequency Pickup Range:
Breaker/Switch Style ATS
101% to (Dropout -1 Hz) of Nominal System Frequency
104%
S2 OF PICK
Hertz
Source 2 Overfrequency Pickup Range:
Breaker/Switch Style ATS
101% to (Dropout -1 Hz) of Nominal System Frequency
104%
TDN
Minutes: Seconds
Time Delay Neutral
0 to 120 seconds
0:00
BAUD RATE
Modbus Baud Rate
9600 or 19200
9600
ADDRESS
Modbus Address
1 to 247
1
PLANT EXER
Days
Plant Exerciser Programming
OFF, DAILY, 7-DAY, 14-DAY or 28 DAY
OFF
PE LOAD XFR
Plant Exerciser Load Transfer
0 or 1 (1 = yes)
0