ATC-300+ Automatic 

Transfer Switch Controller

Section 5: Operation

5.1  General

This section specifically describes the operation and functional 

use of the ATC-300+ Controller.  The practical use of and opera-

tion within each category will be discussed.  In this section, it is 

assumed that prior sections of this manual were reviewed and 

that the operator has a basic understanding of the hardware.

5.2  Automatic Mode

The Automatic Mode of the ATC-300+ Controller provides for 

automatic transfer and re-transfer from Source to Source as dic-

tated by programmed setpoint values.  It provides a summary of 

the ATC-300+ Controller intelligence and supervisory circuits that 

constantly monitor the condition of both the Source 1 and Source 

2 power sources, thus providing the required intelligence for 

transfer operations.  These circuits, for example, automatically ini-

tiate an immediate transfer of power when the power fails or the 

voltage level drops below a preset value.  Exactly what the 

ATC-300+ Controller will initiate in response to a given system 

condition depends upon the combination of standard and selected 

optional features.

5.3  Monitor Mode

Monitor Mode is a special operating mode in which the ATC-

300+ Controller does not provide control for transfer operations.  

The ATC-300+ will, however, continuously monitor both Source 

1 and Source 2 voltages and frequencies.

The ATC-300+ will be in Monitor Mode when the “Monitor 

Mode” control input is in the “Connected” state as described in 

Section 5.4.  While in the Monitor Mode of operation, the ATC-

300+ LCD Display will display “ATS NOT IN AUTOMATIC”.

5.4  Control Inputs

The ATC-300+ has five individual input control signals.  The 

inputs are DC wetted with the unregulated DC supply and appro-

priate current limiting to provide a nominal current of 10 mA per 

channel.

5.4.1 Control Input Descriptions

The Control Input “State” definitions are as follows.

Connected 

- When the input is shorted by an external contact or 

connection.

Unconnected

 - When the input is NOT shorted by an external con-

tact or connection.

The Control Input operations are defined as follows.

Source 1 Closed

When this input is in the “Connected” state, it indicates to the 

ATC-300+ Controller that the Source 1 device is closed.  When 

this input is in the “Unconnected” state, it indicates to the ATC-

300+ that the Source 1 device is open.  This input is typically 

wired to the Source 1 device auxiliary contact that is closed when 

the Source 1 device is closed.  The “Source 1 Closed” input is 

always enabled.

Source 2 Closed

When this input is in the “Connected” state, it indicates to the 

ATC-300+ Controller that the Source 2 device is closed.  When 

this input is in the “Unconnected” state, it indicates to the ATC-

300+ that the Source 2 device is open.  This input is typically 

wired to the Source 2 device auxiliary contact that is closed when 

the Source 2 device is closed.  The Source 2 input is always 

enabled.

Lockout

When the “Lockout” input is in the “Unconnected” state, the ATC-

300+ Controller will not permit an automatic transfer operation.  

When the “Lockout” input is in the “Unconnected” state, the LCD 

Display will be active continuously.  It will read “Lockout” on Line 

2 of the LCD Display screen immediately, regardless of any con-

troller or switching device operation.  When the “Lockout” input is 

in the “Connected” state and the Alarm is reset, the ATC-300+ 

will permit automatic transfer operation.  This input is typically 

wired to the normally closed Source 1 and Source 2 device alarm 

contact that opens when one of the devices has tripped due to a 

fault current.  The “Lockout” input is selectable as enabled or dis-

abled via factory control only.

Go To Source 2

When the “Go to Source 2” input is in the “Connected” state, the 

ATC-300+ Controller is be in a normal, automatic operation 

mode.  When the “Go To Source 2” input is in the “Unconnected” 

state, the ATC-300+ controller will initiate a generator start and 

then transfer to the Source 2 power source.  The ATC-300+ will 

maintain the connection to Source 2 until the input changes to 

the “Connected” state, upon which it will initiate a re-transfer to 

the Source 1 power source.  When the “Go To Source 2” input is 

in the “Unconnected” state, the LCD Display will be active contin-

uously.  Active time delays will be constantly displayed on Line 1, 

with real-time remaining countdown to zero status.  It will con-

stantly read “Go To Source 2” on Line 2 of the LCD Display.  This 

operation is “failsafe”.  The “Go To Source 2” input is always 

enabled.  The “Go To Source 2” input does not have a user acces-

sible programmable setpoint for enable or disable.

Monitor Mode

When the “Monitor Mode” input is in the “Unconnected” state, 

operation of the ATC-300+ Controller will not be effected.  When 

the “Monitor Mode” input is in the “Connected” state, the ATC-

300+ will monitor the Source 1 and Source 2 voltages and fre-

quencies but will not provide any control capabilities.  When the  

“Monitor Mode” input is in the “Connected” state, the ATC-300+ 

LCD Display will be active continuously and will constantly read 

“ATS” on Line 1 and “NOT IN AUTOMATIC” on Line 2 of the LCD 

Display.  The “Monitor Mode” input does not have a user accessi-

ble programmable setpoint for enable or disable.  This is NOT a 

“failsafe” operation.

Manual Re-Transfer

With manual operation set, momentary closure on Pins 5 and 6 of 

Connector J8 allows ATC-300+ to proceed with a re-transfer 

operation at the operators discretion. Should a failure of the emer-

gency source occur while waiting for the manual return, the re-

transfer proceeds automatically. 

Содержание ATC-300+

Страница 1: ...Typical Function of the ATC 300 Controller 13 Operation 15 Programming 20 Troubleshooting and Maintenance 24 Appendix A Display Messages for Status and Timers 26 Appendix B Operational Flowcharts 27 A...

Страница 2: ...TO INSURE THAT PERSONNEL ARE AL ERT TO WARNINGS WHICH APPEAR THROUGHOUT THE DOCUMENT IN ADDITION WARNINGS AND CAUTIONS ARE ALL UPPER CASE AND BOLDFACE COMPL ETELY READ AND UNDERSTAND THE MATERIAL PRE...

Страница 3: ...only available power source and also forces a transfer or re transfer operation to the only available power source Re Transfer Re transfer is defined as a change of the load connection from the Sourc...

Страница 4: ...generator to cool down by running unloaded Timing begins on completion of the re transfer cycle Adjustable 0 1800 Seconds 5 Source 2 Monitoring and Protection This feature provides monitoring and pro...

Страница 5: ...L ED that when lit indicates the load is connected to Source 1 12D Source 2 Source Connected This feature provides a red L ED that when lit indicates the load is connected to Source 2 Power Source Av...

Страница 6: ...ides standard or optional transfer modes mode selec tion devices and operational methods for ATSs 29J Type of Operation MANTR Operation new feature This feature provides for a seletion between an auto...

Страница 7: ...onnected 4 Source 2 Available 5 Source 2 Connected There are seven input functions accessible through the pushbut tons 1 Help Lamp Test 2 Engine Test 3 Step Enter 4 Increase 5 Decrease 6 Alarm Reset 7...

Страница 8: ...entarily illumi nate then the following information will scroll across the display Serial number of the ATC 300 Controller Hardware revision number parts list revision number Software version and revi...

Страница 9: ...when dis cussing the rear access area is with the panel door open and the User fac ing the back of the ATC 300 Controller Located at the left rear of the chassis are connectors J1 J2 and J7 J1 and J2...

Страница 10: ...Style ATS 103 to Dropout 2 of the Nominal System Voltage Underfrequency Dropout Range Breaker Switch Style ATS 90 to 97 of the Nominal System Frequency Underfrequency Pickup Range Breaker Switch Style...

Страница 11: ...g that the phase sequence is reversed 3 1 2 Time Date Display The Time Date Display indicates real time in terms of hours min utes and seconds and month day and year It also indicates individual time...

Страница 12: ...on to step to the TRANSFER HIS TORY message Press the Increase pushbutton to display the most recent transfer event T01 along with the type and cause of the event Press the Decrease pushbutton to disp...

Страница 13: ...will time down if pro grammed and if S1 is available Engine Test or Plant Exercise The K2 relay will energize The S1 connected input MUST open within 6 seconds see above K2 will open IF TDN is pro gr...

Страница 14: ...rmation visit www chfire com IM05805022K Instruction Booklet Page 14 Effective January 2012 ATC 300 Automatic Transfer Switch Controller Figure 4 Connectors on the ATC 300 Controller ATC 300 Controlle...

Страница 15: ...ler that the Source 2 device is closed When this input is in the Unconnected state it indicates to the ATC 300 that the Source 2 device is open This input is typically wired to the Source 2 device aux...

Страница 16: ...ntil the Emergency Inhibit input is de activated 5 5 Output Relay The primary control outputs of the ATC 300 Controller are dry relay contacts These relays are comprised of one latching Form A relay t...

Страница 17: ...IM05805022K For more information visit www chfire com Instruction Booklet Effective January 2012 Page 17 ATC 300 Automatic Transfer Switch Controller Figure 5 Connector Output Relay Connections...

Страница 18: ...in J 5 Pin 6 The pre transfer relay contacts are rated for 10 A 1 3 HP 250 Vac The DC rating is 10 A 30 Vdc 5 5 1 2 Transfer Operations Connections K1 K2 K3 and K4 are factory wired to operate the tra...

Страница 19: ...the Engine Test will be terminated An engine test may also be aborted in the following ways 1 If the Emergency Source does not become available within 90 seconds of the ATC 300 providing the engine st...

Страница 20: ...setpoints while in Program Mode WHILE IN THE PROGRAM MODE THE ATC 300 CONTROLLER IS NEVER OFF LINE AND CONTINUES TO FUNCTION IN ACCORDANCE WITH PREVIOUSLY PROGRAMMED SETPOINTS 6 2 Password To enter th...

Страница 21: ...s and their programmed values Each press of the Step Enter pushbutton will advance the program to the next setpoint Setpoint values CANNOT be changed while in the Display Only Mode 6 4 Change Setpoint...

Страница 22: ...Overvoltage Dropout Range Breaker Switch Style ATS 105 to 120 of Nominal System Voltage 115 S1 OV PICK Volts Source 1 Overvoltage Pickup Range Breaker Switch Style ATS 103 to Dropout 2 of Nominal Sys...

Страница 23: ...Timer 10 to 30 0 20 TDEF Seconds Time Delay Emergency Fail Timer 0 sec to 6 sec 6 SYNC TIME Minutes In phase Transition Synchronization Timer 1 min to 60 min 5 PHASE REV Phase Reversal OFF ABC or CBA...

Страница 24: ...ecifications Replace the unit One or more voltage phases read incorrectly Incorrect wiring ATC 300 is malfunctioning Verify voltage with multimeter Check wiring Replace the unit Verify ground connecti...

Страница 25: ...rvice by factory trained personnel only SYMPTOM PROBABLE CAUSE POSSIBLE SOLUTION S Unit will not perform an Engine Test Engine Test pushbutton was not pressed Display is not displaying the Home screen...

Страница 26: ...R S2 Waiting for the Source 2 source voltage and frequency to become available TD PRE TRAN Countdown timer while waiting for a pre transfer acknowledge input SOURCE 1 DEVICE Indicates that the Source...

Страница 27: ...lable or Engine Test Plant Exercise Go To Emergency TDES timer times out Send Engine Start signal Energize Gen Start relay Is Source 2 Available TDNE timer times out Sends pretransfer signal TPRE time...

Страница 28: ...ring the load Source 1 becomes unavailable or Go To Emergency Is Source 2 Available TDNE timer times out Sends pretransfer signal TPRE timer times out If Source 1 is Available Open Source 1 Energize K...

Страница 29: ...0 02 am Source 1 120 VAC 60Hz Source 2 120 VAC 60Hz S1 FREQ 60 0 S1 Vca 120 S1 Vbc 120 S1 Vab 120 SOURCE 1 GOOD S2 Vab 120 S2 Vbc 120 S2 Vca 120 S2 FREQ 60 0 SOURCE 2 GOOD TIME 10 01 02 AM A TRANSFER...

Страница 30: ...SWORD NEW PASSWORD 0000 Use Inc Dec TDNE 0 00 Use Inc Dec STEP STEP STEP STEP STEP YES STEP STEP STEP STEP STEP B TDES 0 03 Use Inc Dec STEP NEW PASSWORD 0000 Use Inc Dec NEW PASSWORD 0000 Use Inc Dec...

Страница 31: ...c Dec S1 UV PICK 187 Use Inc Dec C S1 OV PICK 228 Use Inc Dec STEP STEP STEP STEP STEP STEP STEP STEP STEP STEP S1 UF DROP 57 0 Use Inc Dec STEP STEP STEP STEP STEP STEP STEP STEP STEP B S2 OV PICK 22...

Страница 32: ...nc Dec PE MINUTE 0 Use Inc Dec TEST MODE 0 Use Inc Dec D VOLT UNBAL 1 Use Inc Dec STEP STEP STEP STEP STEP STEP STEP STEP STEP STEP UNBAL PICK 10 Use Inc Dec STEP STEP STEP STEP STEP STEP STEP STEP ST...

Страница 33: ...c YEAR 2012 Use Inc Dec STEP STEP STEP STEP STEP STEP STEP NO E RESET NO SYSTEM COUNTERS STEP ENGINE RUN 9999 PUSH Alarm Reset RESET NO ALL COUNTERS STEP YES STEP NO D MINUTES 2 Use Inc Dec WEEKDAY 4...

Страница 34: ...Page 34 Effective January 2012 ATC 300 Automatic Transfer Switch Controller S1 AVAIL 9999 PUSH Alarm Reset STEP STEP STEP SAVE YES SETPOINTS E S2 AVAIL 9999 PUSH Alarm Reset LOAD ENERG 9999 PUSH Alarm...

Страница 35: ...94 308 336 389 486 80 96 166 176 192 304 332 384 480 79 95 164 174 190 300 328 379 474 78 94 162 172 187 296 324 374 468 77 92 160 169 185 293 320 370 462 76 91 158 167 182 289 315 365 456 75 90 156 1...

Страница 36: ...47 684 113 136 235 249 271 429 469 542 678 112 134 233 246 269 426 465 538 672 111 133 231 244 266 422 461 533 666 110 132 229 242 264 418 457 528 660 Pickup Breaker 109 131 227 240 262 414 452 523 65...

Страница 37: ...IM05805022K For more information visit www chfire com Instruction Booklet Effective January 2012 Page 37 ATC 300 Automatic Transfer Switch Controller NOTES...

Страница 38: ...For more information visit www chfire com IM05805022K Instruction Booklet Page 38 Effective January 2012 ATC 300 Automatic Transfer Switch Controller NOTES...

Страница 39: ...IM05805022K For more information visit www chfire com Instruction Booklet Effective January 2012 Page 39 ATC 300 Automatic Transfer Switch Controller NOTES...

Страница 40: ...ATION RECOMMENDATIONS AND DESCRIPTIONS CON TAINED HEREIN In no event will EATON be responsible to the purchaser or user in contract in tort including negligence strict liability or otherwise for any s...

Отзывы: