Coonnnneeccttiioonnss
Hazardous voltages are present near the user interface terminal area if the UPS is not totally disconnected.
AVERTISSEMENT!
Des tensions dangereuses sont présentes près de l’enceinte du terminal de l’interface utilisateur si l’onduleur
n’est pas totalement débranché.
Use the procedures in the following paragraphs to connect the TB1, TB2, and TB3 connections.
44..77..11
TTB
B11,, TTB
B22,, aanndd TTB
B33 C
Coonnnneeccttiioonnss ((O
Otthheerr tthhaann TTB
B11 B
Baatttteerryy IInntteerrffaaccee C
Coonnnneeccttiioonnss))
NOTE
When installing interface wiring for TB1, TB2, and TB3 connections, the conduit must be
installed between each device and the UPS cabinet.
NOTE
Terminal block interface wiring must be installed from the top of the UPS cabinet.
To install wiring to connections:
1.
Verify the UPS system is turned off and all power sources are removed. See
for shutdown instructions.
2.
If not already opened, unfasten the front door latch and swing the door open (see
3.
Terminal block TB3 is accessible on the right side of the Minislot communication bay. To gain access to
terminal block TB1, TB2, and the left interface entry conduit landing plates, remove the screws securing
the ISBM deadfront panel and remove the panel. Retain the hardware for later use (see
).
4.
Remove the interface entry conduit landing plates to drill or punch holes (see
5.
Reinstall the interface entry plates and install the conduit.
Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is
required.
AVERTISSEMENT!
Ne pas directement brancher les contacts de relais aux circuits du réseau. Une isolation renforcée des réseaux
est nécessaire.
6.
To locate the appropriate terminals and review the wiring and termination requirements, see paragraph
UPS System Power Wiring Preparation
, and
through
7.
Route the wiring through the wire entry in the Minislot panel (see
)
8.
Wire the connectors to the wires to connect the wiring.
9.
If wiring TB1 battery interface connections, proceed to paragraph
TB1 Battery Interface Connections
if wiring the Minislot connections only, proceed to paragraph
; otherwise,
proceed to Step 10.
10. Reinstall the ISBM deadfront panel and secure with the retained hardware.
Содержание 9395XC
Страница 8: ......
Страница 16: ...xvi Eaton 9395XC UPS 1200kW 1200kVA 1350kW 1350kVA or 1500kW 1500kVA 164001079 Rev 01 List of Figures ...
Страница 18: ...xviii Eaton 9395XC UPS 1200kW 1200kVA 1350kW 1350kVA or 1500kW 1500kVA 164001079 Rev 01 List of Tables ...
Страница 26: ...8 Eaton 9395XC UPS 1200kW 1200kVA 1350kW 1350kVA or 1500kW 1500kVA 164001079 Rev 01 Introduction ...
Страница 118: ...100 Eaton 9395XC UPS 1200kW 1200kVA 1350kW 1350kVA or 1500kW 1500kVA 164001079 Rev 01 Understanding UPS Operation ...
Страница 160: ...16400107901 164001079 01 ...