Eaton 9395XC UPS 1200kW/1200kVA, 1350kW/1350kVA or 1500kW/1500kVA 164001079—Rev 01
29
For a UPS with common rectifier input terminals, E1 through E11 are 2-hole bus bar mountings for standard
NEMA 2-hole barrel lugs. The power wiring connections for this equipment are rated at 90ºC. See
for
external power cable terminations,
for supplied external wiring terminal hardware, and
for
recommended installation parts and tools not supplied by Eaton Corporation.
through
show the location of the power cable terminals inside the UPS.
Table 8. External Power Cable Terminations
Terminal Function
Terminal
Function
Bus Landings
(using both sides of bus)
Tightening Torque
Nm (lb ft)
Bolt Size
AC Input to UPS
Rectifier
E1
Phase A
9 – 2 bolt mounting
76 (56)
M12
E2
Phase B
9 – 2 bolt mounting
76 (56)
M12
E2
Phase C
9 – 2 bolt mounting
76 (56)
M12
AC Input to Bypass
E6
Phase A
9 – 2 bolt mounting
76 (56)
M12
E7
Phase B
9 – 2 bolt mounting
76 (56)
M12
E8
Phase C
9 – 2 bolt mounting
76 (56)
M12
AC Output to Critical
Load
E9
Phase A
8 – 2 bolt mounting
76 (56)
M12
E10
Phase B
8 – 2 bolt mounting
76 (56)
M12
E11
Phase C
8 – 2 bolt mounting
76 (56)
M12
DC Input from
Battery or Battery
Disconnect to UPS
E4
Battery (+)
12 – 2 bolt mounting
76 (56)
M12
E5
Battery (-)
12 – 2 bolt mounting
76 (56)
M12
NOTE Customer ground, sized in accordance with NEC Table 250.122, can be run in any conduit listed in
.
Содержание 9395XC
Страница 8: ......
Страница 16: ...xvi Eaton 9395XC UPS 1200kW 1200kVA 1350kW 1350kVA or 1500kW 1500kVA 164001079 Rev 01 List of Figures ...
Страница 18: ...xviii Eaton 9395XC UPS 1200kW 1200kVA 1350kW 1350kVA or 1500kW 1500kVA 164001079 Rev 01 List of Tables ...
Страница 26: ...8 Eaton 9395XC UPS 1200kW 1200kVA 1350kW 1350kVA or 1500kW 1500kVA 164001079 Rev 01 Introduction ...
Страница 118: ...100 Eaton 9395XC UPS 1200kW 1200kVA 1350kW 1350kVA or 1500kW 1500kVA 164001079 Rev 01 Understanding UPS Operation ...
Страница 160: ...16400107901 164001079 01 ...