![Eaton 9315 Скачать руководство пользователя страница 74](http://html.mh-extra.com/html/eaton/9315/9315_installation-manual_527094074.webp)
DESCRIPTION:
DATE:
DRAWING NO:
1 of 1
UPS SYSTEM ONELINE CONFIGURATIONS
SHEET:
REVISION:
F
164201118−3
041500
NOTE 2: Output Voltage must match Bypass Input Voltage.
NOTE 1: A bypass neutral feeder must be supplied when the output neutral is used. If no
bypass neutral is supplied, the output neutral is
to be bonded to ground
through a minimum 3/0 copper conducter.
Customer Information
A−22
EATON
Powerware
®
9315 UPS (300–500 kVA) Installation Manual
S
164201118 Rev H
www.powerware.com
Table U. UPS System Oneline Configurations
Oneline Drawing
164201118−4
Powerware 9315
Vin / Vout
Input
Transformer
Output
Transformer
Sheet 1
400, 500
480/480
N/A
N/A
300, 400
400/400
N/A
N/A
Sheet 2
400, 500
480/480
Isolation
(Delta in, Delta out)
N/A
Sheet 2
500
600/600
Isolation
(Delta in, Delta out)
N/A
Sheet 3
500
480/480
5% Input Filter
(Delta in, Delta out)
N/A
Sheet 4
400
(Single Feed)
208/208
Isolation
(Wye in, Wye out)
Auto
Sheet 5
400
(Dual Feed)
208/208
Isolation
(Wye in, Wye out)
Auto
Содержание 9315
Страница 1: ...Powerware 9315 UPS 300 500 kVA Installation Manual ...
Страница 97: ......