SECUREMENT OF CABLE
NYLON ROPE −
3/8 inch (9.5 mm)
diameter. Minimum
of five wraps.
6 inches (152 mm)
164201118−1
INSTALLATION NOTES
10 of 19
Customer Information
A−11
EATON
Powerware
®
9315 UPS (300–500 kVA) Installation Manual
S
164201118 Rev H
www.powerware.com
8.
When using 65 KAIC or higher rated breakers, secure cables as shown in figure below.
Wrap line cables together with nominal 3/8 inch (9.5mm) nylon rope or rope having a
minimum tensile strength of 2000 pounds (8896 N). Wrap line cables at 6 inches (152 mm)
and 12 inches (305 mm) from the line terminals with five wraps. Wrap each additional 6
inch (152.4 mm) interval with five wraps or 1 inch (25.4 mm) intervals with one wrap