![Eaton 9315 Скачать руководство пользователя страница 21](http://html.mh-extra.com/html/eaton/9315/9315_installation-manual_527094021.webp)
4−1
EATON
Powerware
®
9315 UPS (300–500 kVA) Installation Manual
S
164201118 Rev H
www.powerware.com
Chapter 4
Installing Battery Cabinets
This chapter describes installing the UPS manufacturer’s battery cabinets. If you are
installing battery cabinets and remote disconnects provided by Powerware, refer to the
Powerware 9315 Series 685 and 1085 Auxiliary Battery Cabinets Installation Manual
for
instructions.
One model is available: the Series 1085 (1085−mm wide cabinet).
4.1 Important Safety Instructions
The installation of battery cabinets should be performed or supervised by personnel
knowledgeable of batteries and their associated precautions. Keep unauthorized personnel
away from battery cabinets.
Observe these precautions when working on or around battery cabinets:
A
Remove watches, rings, or other metal objects.
A
Use tools with insulated handles.
A
Wear rubber gloves and boots.
A
Do not lay tools or metal parts on top of batteries or battery cabinets.
A
Disconnect the charging source prior to connecting or disconnecting terminals.
A
Determine if the battery is inadvertently grounded. If it is, remove the source of the
ground. Any part of a grounded battery can result in electrical shock. The likelihood of
such shock is reduced if such grounds are removed during installation and maintenance.
A
When replacing batteries, use the same number of sealed, lead-acid batteries.
A
Proper disposal of batteries is required. Refer to your local codes for disposal
requirements.