Customer Information
A−18
EATON
Powerware
®
9315 UPS (300–500 kVA) Installation Manual
S
164201118 Rev H
www.powerware.com
1.
Use Class 1 wiring methods (as defined by the NEC) for control wiring. Install the control
wiring in separate conduit from the power wiring. The wire should be rated at 24 volts,
1 amp minimum.
2.
Refer to Table Q, Table R, and Table S, and to applicable chapters for information about
installing control wiring for options and accessories.
Table Q. Control Wiring Terminations
Terminal
Description
Terminal Function
TB1
Terminal Block
Building Alarms (optional, up to 6)
Generator Interface
TB1
TB2
TB2
Terminal Block
Remote EPO
On Inverter" Monitoring
On Bypass" Monitoring
Summary Alarm & Notice Contacts
Table R. Summary Alarm Relay Contacts
14
15
13
11
12
10
RELAY 1
TB2
RELAY 2
CONTACT RATING:
Maximum Switched Voltage
32 VAC 42 VDC
Maximum Carrying Current
1A