![Eaton 9315 Скачать руководство пользователя страница 51](http://html.mh-extra.com/html/eaton/9315/9315_installation-manual_527094051.webp)
Installing a Supervisory Contact Module
11−3
EATON
Powerware
®
9315 UPS (300–500 kVA) Installation Manual
S
164201118 Rev H
www.powerware.com
7.
If you are installing an RMP or RIM in addition to an SCM, proceed to Chapter 9
or 10, respectively; otherwise, secure the UPS cabinet by reversing the steps on
page 3−4.
Table 11-1. SCM Wire Terminations
From SCM A
To UPS
Remarks
TB1−4
TB3−1
Twisted wires (4)
1−2 turns per 3
″
TB1−5
TB3−2
TB1−6
TB3−3
TB1−7
TB3−4
From SCM B (if used)
To UPS
Remarks
TB1−4
TB3−5
Twisted wires (4)
1−2 turns per 3
″
TB1−5
TB3−6
TB1−6
TB3−7
TB1−7
TB3−8