Installing Input and Output Transformers and Input Filter Cabinets
5−6
EATON
Powerware
®
9315 UPS (300–500 kVA) Installation Manual
S
164201118 Rev H
www.powerware.com
4.
Close the rectifier input transformer cabinet doors and the bypass input
transformer cabinet doors.
Table 5-2. Rectifier Input Transformer and Input Filter Connection Points (Dual
Feed)
Connection Point in Transformer or Input Filter Cabinet
Connection Point
in UPS
Phase
Input
Output
∅
A
E23
E26
E1
∅
B
E24
E27
E2
∅
C
E25
E28
E3
Neutral
E22
E29
E12
Table 5-3. Bypass Input Transformer Connection Points (Dual Feed)
Connection Point in Transformer Cabinet
Connection Point
in UPS
Phase
Input
Output
∅
A
E23
E26
E6
∅
B
E24
E27
E7
∅
C
E25
E28
E8
Neutral
E22
E29
E12
To wire the output transformer cabinet:
NOTE
For wiring information, see drawing 164201118−1 and Table B, Table F, Table G,
and Table H in Appendix A.
1.
Install wiring from UPS cabinet to transformer cabinet using conduit through cable
entry panel in the top of cabinet.
2.
Install wiring from input transformer cabinet to UPS cabinet using conduit through
the cable entry panels in the top of the UPS.
3.
Connect the cables as shown in Table F on page A−7. See Figure 5-8 on page 5−10
for location of connection points within the transformer cabinets.
Table 5-4. Output Transformer Connection Points
Connection Point in Transformer Cabinet
Connection point
in UPS
Phase
Input
Output
∅
A
E23
E26
E9
∅
B
E24
E27
E10
∅
C
E25
E28
E11
Neutral
E29
E29
E12