Page 5-43
IL17569
Effective June, 2001
Figure 5-3. Logic Setting Flowchart
Logic Gates 1
All six logic gates contain the same
through 6:
settings as shown below.
Function:
Set to OR, AND, NOR, NAND, Disable. The
Function setting defines the output of the logic
gates with inputs IN1, IN2, IN3, and IN4. The
default setting is OR.
Setting Group:
This setting defines the Setting Group for which
the logic gate programming is active. This
setting is also linked to the System Config
settings, which is where the total number of
settings groups (1 to 4) is programmed.
IN1, IN2, IN3, IN4:
These settings define the logic inputs to Logic
Gates 1 through 6. See the settings table and
Section 9.6 for a complete description of the
logic input settings.
Timer Gates 1
All six timer gates contain the same settings as
through 6:
shown below.
Setting Group:
This setting defines the Setting Group for which
the timer gate programming is active. This
setting is also linked to the System Config
settings, which is where the total number of
settings groups (1 to 4) is programmed.
Содержание 66D2041G01
Страница 1: ...IL17569 Effective June 2001 Instructions for FP 5000 Protective Relay ...
Страница 7: ...IL17569 Table of Contents 6 Effective June 2001 This page left blank intentionally ...
Страница 13: ...IL17569 Page 2 2 Effective June 2001 Figure 2 2 FP 5000 Simple Wye Connected Application ...
Страница 14: ...Page 2 3 IL17569 Effective June 2001 Figure 2 3 FP 5000 Simple Open Delta Application ...
Страница 19: ...IL17569 Page 2 8 Effective June 2001 This page left blank intentionally ...
Страница 25: ...IL17569 Page 3 6 Effective June 2001 This page left blank intentionally ...
Страница 98: ...IL17569 Page 5 50 Effective June 2001 This page left blank intentionally ...
Страница 105: ...Page 6 7 IL17569 Effective June 2001 Figure 6 8 Voltage Wye Input Wiring Options and Connection Schematics ...
Страница 106: ...IL17569 Page 6 8 Effective June 2001 Figure 6 9 Voltage Delta Input Wiring Options and Connection Schematics ...
Страница 108: ...IL17569 Page 6 10 Effective June 2001 Figure 6 10 Common Ct Wiring Configurations ...
Страница 141: ...IL17569 Page 11 4 Effective June 2001 This page left blank intentionally ...
Страница 165: ...IL17569 Page Appendix 6 Effective June 2001 Figure 13 2 ANSI Very Inverse ...
Страница 166: ...Page Appendix 7 IL17569 Effective June 2001 Figure 13 3 ANSI Extremely Inverse ...
Страница 167: ...IL17569 Page Appendix 8 Effective June 2001 Figure 13 4 IEC A Figure 13 4 IEC A ...
Страница 168: ...Page Appendix 9 IL17569 Effective June 2001 Figure 13 5 IEC B ...
Страница 169: ...IL17569 Page Appendix 10 Effective June 2001 Figure 13 6 IEC C ...
Страница 170: ...Page Appendix 11 IL17569 Effective June 2001 Figure 13 7 IEC ...
Страница 171: ...IL17569 Page Appendix 12 Effective June 2001 Figure 13 8 ANSI ...
Страница 172: ...Page Appendix 13 IL17569 Effective June 2001 Figure 13 9 Thermal ...
Страница 173: ...IL17569 Page Appendix 14 Effective June 2001 Figure 13 10 Phase I4 t ...
Страница 174: ...Page Appendix 15 IL17569 Effective June 2001 Figure 13 11 Phase I2 t ...
Страница 175: ...IL17569 Page Appendix 16 Effective June 2001 Figure 13 12 Phase It ...
Страница 176: ...Page Appendix 17 IL17569 Effective June 2001 Figure 13 13 Phase 12 I4 t ...
Страница 177: ...IL17569 Page Appendix 18 Effective June 2001 Figure 13 14 Phase I2 t ...
Страница 178: ...Page Appendix 19 IL17569 Effective June 2001 Figure 13 15 Ground IT ...
Страница 180: ...Page Appendix 21 IL17569 Effective June 2001 This page left blank intentionally ...
Страница 187: ...Publication No IL17569 June 2001 Pittsburgh Pennsylvania U S A ...