Page 4-7
IL17569
Effective June, 2001
4.6.1.3 Selecting the “Energy” Sub-menu
This section allows the user to view the following Energy param-
eters (See
Display 4.6
).
• Watt Energy Hours (Forward, Reverse, Net)
• Var Energy Hours (Lead, Lag, Net)
• VA Hours
• Start Date and Time stamp the Unit started measuring
Display 4.6 Energy Sub-menu
The FP-5000 uses the positive sign convention for power measure-
ment. A positive sign convention corresponds to:
• Inductive load = lagging power factor = positive Var and power
factor values.
• Capacitive load = leading power factor = negative Var and power
factor values.
Hence the Forward watt-hours and the Lagging Var-hours are
positive, while the Reverse watt-hour and the Leading Var-hour
displays represent negative values.
The Forward watt-hours, Reverse watt-hours, Leading Var-hours,
Lagging Var-hours and VA-hours are all displayed as unsigned
numbers. However, when the FP-5000 calculates the Net watt-hours
and the Net Var-hours, the calculation is based on the sign
convention, therefore the Net watt-hours and the Net Var-hours can
be positive or negative values. Refer to the Power Quadrant
diagram in
Figure 4.4
.
A lagging power factor is displayed as a positive value and a
leading power factor is displayed as a negative value. The maxi-
mum power factor is the most lagging power factor value measured
by the FP-5000 and the minimum power factor is the most leading
power factor value measured. Two examples for min/max power
factor values are shown in
Figure 4.3
.
The following examples define the sign convention for energy under
various power flow conditions:
•
Induction Motor Load (
Figures 4.4
and
4.5
)
Typically when monitoring induction motor loads, the power flow is
in Quadrant 4. The watts are positive and the power factor is
lagging. By definition, the power factor and Vars are positive.
•
Capacitive Load (
Figure 4.4
)
When monitoring a capacitive load or a heavily excited synchro-
nous motor, the power flow is in Quadrant 1. By definition, the
power factor and Vars are negative.
System Watt Hour
Fwd kWh
Magnitude
Rev kWh
Magnitude
Net kWh
Magnitude
System var Hours
Lead kvarh Magnitude
Lag kvarh Magnitude
Net kvarh
Magnitude
System VA Hours
kVAh
Magnitude
Start Date
Date
mm/dd/yy
Time
hh:mm:ss
QUADRANT 2
QUADRANT 1
Watts Negative
Watts Positive
Vars Negative
Vars Negative
Power Factor Lagging (+)
Power Factor Leading (-)
Real Power
Watts Negative
Watts Positive
Vars Positive
Vars Positive
Power Factor Leading (-)
Power Factor Lagging (+)
QUADRANT 3
QUADRANT 4
Reactive Power
Figure 4-4. Power Quadrants
Figure 4-3. Power Factor Minimum/Maximum
Содержание 66D2041G01
Страница 1: ...IL17569 Effective June 2001 Instructions for FP 5000 Protective Relay ...
Страница 7: ...IL17569 Table of Contents 6 Effective June 2001 This page left blank intentionally ...
Страница 13: ...IL17569 Page 2 2 Effective June 2001 Figure 2 2 FP 5000 Simple Wye Connected Application ...
Страница 14: ...Page 2 3 IL17569 Effective June 2001 Figure 2 3 FP 5000 Simple Open Delta Application ...
Страница 19: ...IL17569 Page 2 8 Effective June 2001 This page left blank intentionally ...
Страница 25: ...IL17569 Page 3 6 Effective June 2001 This page left blank intentionally ...
Страница 98: ...IL17569 Page 5 50 Effective June 2001 This page left blank intentionally ...
Страница 105: ...Page 6 7 IL17569 Effective June 2001 Figure 6 8 Voltage Wye Input Wiring Options and Connection Schematics ...
Страница 106: ...IL17569 Page 6 8 Effective June 2001 Figure 6 9 Voltage Delta Input Wiring Options and Connection Schematics ...
Страница 108: ...IL17569 Page 6 10 Effective June 2001 Figure 6 10 Common Ct Wiring Configurations ...
Страница 141: ...IL17569 Page 11 4 Effective June 2001 This page left blank intentionally ...
Страница 165: ...IL17569 Page Appendix 6 Effective June 2001 Figure 13 2 ANSI Very Inverse ...
Страница 166: ...Page Appendix 7 IL17569 Effective June 2001 Figure 13 3 ANSI Extremely Inverse ...
Страница 167: ...IL17569 Page Appendix 8 Effective June 2001 Figure 13 4 IEC A Figure 13 4 IEC A ...
Страница 168: ...Page Appendix 9 IL17569 Effective June 2001 Figure 13 5 IEC B ...
Страница 169: ...IL17569 Page Appendix 10 Effective June 2001 Figure 13 6 IEC C ...
Страница 170: ...Page Appendix 11 IL17569 Effective June 2001 Figure 13 7 IEC ...
Страница 171: ...IL17569 Page Appendix 12 Effective June 2001 Figure 13 8 ANSI ...
Страница 172: ...Page Appendix 13 IL17569 Effective June 2001 Figure 13 9 Thermal ...
Страница 173: ...IL17569 Page Appendix 14 Effective June 2001 Figure 13 10 Phase I4 t ...
Страница 174: ...Page Appendix 15 IL17569 Effective June 2001 Figure 13 11 Phase I2 t ...
Страница 175: ...IL17569 Page Appendix 16 Effective June 2001 Figure 13 12 Phase It ...
Страница 176: ...Page Appendix 17 IL17569 Effective June 2001 Figure 13 13 Phase 12 I4 t ...
Страница 177: ...IL17569 Page Appendix 18 Effective June 2001 Figure 13 14 Phase I2 t ...
Страница 178: ...Page Appendix 19 IL17569 Effective June 2001 Figure 13 15 Ground IT ...
Страница 180: ...Page Appendix 21 IL17569 Effective June 2001 This page left blank intentionally ...
Страница 187: ...Publication No IL17569 June 2001 Pittsburgh Pennsylvania U S A ...