IL17569
Page 8-8
Effective June, 2001
Figure 8-10. Zone Interlocking Example with FP-5000 and DT-3000
In general, if the Zone Interlocking Input is enabled, the absence of
a zone-in signal active, and an IOC or TOC pickup occurs, an
immediate trip will occur. The immediate trip has a 3-cycle pickup
delay to make sure the downstream devices have a chance to
activate the zone interlock signal. If the zone-in signal is active, then
the programmed delay time is used.
If the Zone In setpoint is set to “Phase” then any phase current
above of the IOC pickup or
1.5 times
the TOC pickup will cause an
immediate trip in the absence of an active zone-in signal. Ground or
residual current IOC or TOC will not cause an immediate trip. The
1.5 time multiplier is used so that a low level current overload does
not cause an immediate trip. If the zone-in signal is active then the
programmed delay time is used.
If the Zone In setpoint is set to “Ground” then any ground or residual
current above the IOC pickup or the TOC pickup will cause an
immediate trip in the absence of an active zone-in signal. Phase
current IOC or TOC will not cause an immediate trip. If the zone-in
signal is active then the programmed delay time is used.
In the case that the breaker that is taking action fails to open the
circuit, the zone-out signal is removed in one of two ways:
1. If the breaker fail function is active then the zone out signal is
immediately removed. See Section 5 Programming on page 5-1
and Section 8.9 Breaker-Oriented Functions.
2. If the protective relay has operated but the current is still sensed,
the zone-out signal is removed 10 cycles after the operation.
Содержание 66D2041G01
Страница 1: ...IL17569 Effective June 2001 Instructions for FP 5000 Protective Relay ...
Страница 7: ...IL17569 Table of Contents 6 Effective June 2001 This page left blank intentionally ...
Страница 13: ...IL17569 Page 2 2 Effective June 2001 Figure 2 2 FP 5000 Simple Wye Connected Application ...
Страница 14: ...Page 2 3 IL17569 Effective June 2001 Figure 2 3 FP 5000 Simple Open Delta Application ...
Страница 19: ...IL17569 Page 2 8 Effective June 2001 This page left blank intentionally ...
Страница 25: ...IL17569 Page 3 6 Effective June 2001 This page left blank intentionally ...
Страница 98: ...IL17569 Page 5 50 Effective June 2001 This page left blank intentionally ...
Страница 105: ...Page 6 7 IL17569 Effective June 2001 Figure 6 8 Voltage Wye Input Wiring Options and Connection Schematics ...
Страница 106: ...IL17569 Page 6 8 Effective June 2001 Figure 6 9 Voltage Delta Input Wiring Options and Connection Schematics ...
Страница 108: ...IL17569 Page 6 10 Effective June 2001 Figure 6 10 Common Ct Wiring Configurations ...
Страница 141: ...IL17569 Page 11 4 Effective June 2001 This page left blank intentionally ...
Страница 165: ...IL17569 Page Appendix 6 Effective June 2001 Figure 13 2 ANSI Very Inverse ...
Страница 166: ...Page Appendix 7 IL17569 Effective June 2001 Figure 13 3 ANSI Extremely Inverse ...
Страница 167: ...IL17569 Page Appendix 8 Effective June 2001 Figure 13 4 IEC A Figure 13 4 IEC A ...
Страница 168: ...Page Appendix 9 IL17569 Effective June 2001 Figure 13 5 IEC B ...
Страница 169: ...IL17569 Page Appendix 10 Effective June 2001 Figure 13 6 IEC C ...
Страница 170: ...Page Appendix 11 IL17569 Effective June 2001 Figure 13 7 IEC ...
Страница 171: ...IL17569 Page Appendix 12 Effective June 2001 Figure 13 8 ANSI ...
Страница 172: ...Page Appendix 13 IL17569 Effective June 2001 Figure 13 9 Thermal ...
Страница 173: ...IL17569 Page Appendix 14 Effective June 2001 Figure 13 10 Phase I4 t ...
Страница 174: ...Page Appendix 15 IL17569 Effective June 2001 Figure 13 11 Phase I2 t ...
Страница 175: ...IL17569 Page Appendix 16 Effective June 2001 Figure 13 12 Phase It ...
Страница 176: ...Page Appendix 17 IL17569 Effective June 2001 Figure 13 13 Phase 12 I4 t ...
Страница 177: ...IL17569 Page Appendix 18 Effective June 2001 Figure 13 14 Phase I2 t ...
Страница 178: ...Page Appendix 19 IL17569 Effective June 2001 Figure 13 15 Ground IT ...
Страница 180: ...Page Appendix 21 IL17569 Effective June 2001 This page left blank intentionally ...
Страница 187: ...Publication No IL17569 June 2001 Pittsburgh Pennsylvania U S A ...