Page 36
I.B. 70A2580H02
Effective November 2012 Style
70A2580H02
Printed in USA
6-12 TROUBLESHOOTING CHART
SYMPTOM
INSPECTION AREA
PROBABLE DEFECTS
Undesirably Closes
•
Control Circuit
• Close Circuit
(CS/C Getting Shorted)
•
Mechanism
• Close Release Latch
(Fails to reset)
• Close Floor Tripper
(Fails to reset)
Fails To Trip
• Control Circuit
• Control Power
(Fuse blown or switch off)
• Secondary Disconnect
• Auxiliary Switch
(a contact not making, poor or burned)
• Trip Coil
(Burned or open)
• Terminals and Connections
(Poor or burned or open)
• No Trip Sound
• Trip Mechanism
• Trip Clapper
(Jammed)
• Trip Mechanism
• Trip Bar, Trip Latch
(Jammed)
• Pole Shaft
(Jammed)
• Operating Rod Assembly
(Broken or pins out)
• Trip Sound
But No Trip
• Vacuum Interrupter
(One or more welded)
Undesirably Trips
• Control Circuit
• Control Power
(CS/T Switch, remains made)
• Mechanism
• Trip Coil Clapper
(Not resetting)
• Trip Bar or Trip Latch
(Poor engagement of mating
or worn surfaces)
• Trip Bar Reset Spring
(Loss of torque)
• Tip of Main Cam Chipped or Worn
(Trip after Closed Breaker is Charged)
Содержание 380 VCP-Wind
Страница 2: ......
Страница 23: ...I B 70A2580H02 Page 17 Effective November 2012 Figure 5 2 Closing Cam and Trip Linkage ...
Страница 25: ...I B 70A2580H02 Page 19 Effective November 2012 Figure 5 3 Charging Schematic ...
Страница 26: ...Page 20 I B 70A2580H02 Effective November 2012 Figure 5 4 Typical VCP Wind DC Control Schematics ...
Страница 27: ...I B 70A2580H02 Page 21 Effective November 2012 Figure 5 5 Typical VCP Wind AC Control Schematics ...
Страница 47: ...I B 70A2580H02 Page 41 Effective November 2012 Table 7 2 38kV VCP Wind Mini Module Code Pin Position Chart ...
Страница 49: ...I B 70A2580H02 Page 43 Effective November 2012 ...