I.B. 70A2580H02
Page 13
Effective November 2012
Figure 4-2 VCP-Wind Breaker insertion Step 1, Push
Breaker into Mini Module as shown.
Figure 4-3 VCP-Wind Breaker insertion Step 2, Pull in
Handles
Figure 4-4 VCP-Wind Breaker insertion Step 3, Push in
circuit breaker to the DISCONNECT position. Note: You
can not rack the breaker in this position.
Figure 4-5 VCP-Wind Breaker insertion Step 4, pull in
shoot bolt handles and push circuit breaker to the
TEST position. Note: Secondaries automatically
engage. Breaker can now be racked in.
Figure 4-6 VCP-Wind Breaker insertion Step 5, Use
Levering tool and lever breaker to the CONNECT
Position. (Levering completed, shown above)
Push handle inward while levering in (clockwise) or
levering out (counter clockwise)
Levering Trip Free Interlocks
Internal to the breaker are interlocks that render the
circuit breaker mechanism mechanically and
electrically trip free during the levering process.
Anti-Close Interlock
This interlock prevents releasing the closing springs
electrically or manually if the circuit breaker is already
closed.
Содержание 380 VCP-Wind
Страница 2: ......
Страница 23: ...I B 70A2580H02 Page 17 Effective November 2012 Figure 5 2 Closing Cam and Trip Linkage ...
Страница 25: ...I B 70A2580H02 Page 19 Effective November 2012 Figure 5 3 Charging Schematic ...
Страница 26: ...Page 20 I B 70A2580H02 Effective November 2012 Figure 5 4 Typical VCP Wind DC Control Schematics ...
Страница 27: ...I B 70A2580H02 Page 21 Effective November 2012 Figure 5 5 Typical VCP Wind AC Control Schematics ...
Страница 47: ...I B 70A2580H02 Page 41 Effective November 2012 Table 7 2 38kV VCP Wind Mini Module Code Pin Position Chart ...
Страница 49: ...I B 70A2580H02 Page 43 Effective November 2012 ...