I.B. 70A2580H02
Page 27
Effective November 2012
6-3 INSPECTION AND MAINTANENCE PROCEDURES
No./Section
Inspection Item
Criteria
Inspection Method
Corrective Action
1. Insulation
Insulation
Integrity
Drive Insulator
and
Molded Pole Unit Support
Main Circuit to Ground
Between Main Circuit
Terminals
Control Circuit to Ground
No dirt
and
No cracking
Withstand
Withstand
Withstand
Visual Check
Visual Check
Hipot Tester
Hipot Tester
Hipot Tester
Clean with lint-free cloth
or
Replace cracked unit
Clean and retest or replace
Clean and retest or replace
Clean and retest or replace
2. Power
Elements
Vacuum Interrupters
Primary Disconnects
Precise Measure-
ment from rear
Adequate Vacuum
No burning or damage
Measurement - Close the circuit
breaker and proceed as described
in Paragraph 6-5
Proceed with integrity check as
described in Paragraph 6-4
Visual Check
If the front indicator marks are
in the red area and the rear
measurement is not acceptable,
replace pole unit assembly
If integrity check is not satisfactory,
replace pole unit assembly
Replace if burned, damaged, or eroded
3. Control
Circuit
Parts
Closing and Tripping Device
Including Disconnects
Wiring
Terminals
Motor
Smooth and correct
operation by control
power
Securely tied in
proper place
Tight
Smooth, Normal
Operation
Test closing and tripping of the
circuit breaker twice
Visual Check
Visual Check
Functional Test
Replace any defective device. Identify
per trouble-shooting chart
Repair or tie as necessary
Tighten or replace if necessary
Replace brushes or motor
4. Operating
Mechanism
Tightness of Hardware
Dust or Foreign Matter
Lubrication
Deformation or Excessive
Wear
Manual Operation
No loose or missing
parts
No dust or foreign
matter
Smooth operation
and no excessive
wear
No excessive
deformation or wear
Smooth operation
Visual and by feel
Visual Check
Sight, feel and per maintenance
schedule
Visual and operational
Manual charging, closing
and tripping
Refer to Table
6 . 1
and tighten
or reinstate if necessary with
appropriate tools
Clean as necessary
Refer to Figure
6 - 1 ,
Paragraph
6-11 and lubricate very spar-
ingly with light machine oil
Remove cause and replace parts
Correct per troubleshooting
chart if necessary
Содержание 380 VCP-Wind
Страница 2: ......
Страница 23: ...I B 70A2580H02 Page 17 Effective November 2012 Figure 5 2 Closing Cam and Trip Linkage ...
Страница 25: ...I B 70A2580H02 Page 19 Effective November 2012 Figure 5 3 Charging Schematic ...
Страница 26: ...Page 20 I B 70A2580H02 Effective November 2012 Figure 5 4 Typical VCP Wind DC Control Schematics ...
Страница 27: ...I B 70A2580H02 Page 21 Effective November 2012 Figure 5 5 Typical VCP Wind AC Control Schematics ...
Страница 47: ...I B 70A2580H02 Page 41 Effective November 2012 Table 7 2 38kV VCP Wind Mini Module Code Pin Position Chart ...
Страница 49: ...I B 70A2580H02 Page 43 Effective November 2012 ...