
I.B. 70A2580H02
Page 11
Effective November 2012
SECTION 4: INITIAL INSPECTION AND
INSTALLATION
4-1 INTRODUCTION
WARNING
BEFORE PLACING THE CIRCUIT BREAKER IN
SERVICE, CAREFULLY FOLLOW THE
INSTALLATION PROCEDURE GIVEN BELOW. NOT
FOLLOWING THE PROCEDURE CAN FAIL TO
UNCOVER SHIPPING DAMAGE THAT MAY RESULT
IN INCORRECT CIRCUIT BREAKER OPERATION
LEADING TO DEATH, BODILY INJURY, AND
EQUIPMENT DAMAGE.
Before attempting to place a circuit breaker in service, it
should be carefully examined and operated manually and
electrically. In addition, carefully examine the breaker for
loose or obviously damaged parts. The following
information is a guide for performing recommended
checks and tests.
4-2 MANUAL OPERATION CHECK
Refer to Figures 3-4
and 4-1
and then proceed by placing
the maintenance tool into the manual charge socket
opening. Charge the closing springs with about 36 up
and down strokes of the handle. When charging is
complete the closing crank goes over center with an
audible
CLICK
and the springs Charged/Discharged
indicator shows “Charged.”
NOTICE
If the springs are to be charged on a closed circuit
breaker, no click is heard at the end of charging
operation. Discontinue charging and remove the
maintenance tool as soon as “Charged” flag is fully
visible. Continued attempts to charge further may
result in damage to the mechanism.
Remove the maintenance tool. Close and trip the circuit
breaker. Repeat several times.
4-3 VACUUM INTERRUPTER INTEGRITY
Using a dry, lint free cloth or paper towel, clean all the
accessible insulating surfaces of the pole units. Conduct a
vacuum interrupter integrity check as described in
Section 6-4.
4-4 INSULATION
Check the circuit breaker’s primary and secondary
insulation as described in Section 6-6.
4-5 CONTACT EROSION AND WIPE
Eaton vacuum interrupters used on the 38kV VCP-
Wind are designed to achieve very low arc voltages
and short arc times, resulting in very low arc
energy. Contact wear is therefore negligible.
4-6 PRIMARY CIRCUIT RESISTANCE
Check the primary circuit resistance as described in
Section 6-7. The resistance should not exceed the
values specified. Record the values obtained for
future reference.
4-7 NAMEPLATE
Compare the circuit breaker nameplate information
with switchgear drawings for compatibility.
4-8 ELECTRICAL OPERATION CHECK
After having completed all previous checks and tests,
the circuit breaker is ready to be operated electrically.
It is preferred that this check be made with the circuit
breaker in the TEST position or by using a test
jumper, if the circuit breaker is outside the cell
structure.
Figure 4-1 Type VCP-Wind Circuit Breaker Manual
Charging Handle in Use
Содержание 380 VCP-Wind
Страница 2: ......
Страница 23: ...I B 70A2580H02 Page 17 Effective November 2012 Figure 5 2 Closing Cam and Trip Linkage ...
Страница 25: ...I B 70A2580H02 Page 19 Effective November 2012 Figure 5 3 Charging Schematic ...
Страница 26: ...Page 20 I B 70A2580H02 Effective November 2012 Figure 5 4 Typical VCP Wind DC Control Schematics ...
Страница 27: ...I B 70A2580H02 Page 21 Effective November 2012 Figure 5 5 Typical VCP Wind AC Control Schematics ...
Страница 47: ...I B 70A2580H02 Page 41 Effective November 2012 Table 7 2 38kV VCP Wind Mini Module Code Pin Position Chart ...
Страница 49: ...I B 70A2580H02 Page 43 Effective November 2012 ...