A proportional-action controller (P controller) changes the manipulated variable M proportional
to the loop error. The P controller works immediately. By itself it cannot drive the loop error to
zero.
:Manipulated variable of the P controller at the time n
:Gain of the P controller
: Loop error at the time n
The following picture shows a jump in process value and step response of the controller:
Summary
The P controller has the following characteristics:
It cannot correct faults with the control process > lasting loop error.
It reacts immediately to a change in the process value.
It is stable.
I Controller
An integral-action controller (I controller) changes the manipulated variable M proportional to
the loop error and to the time. The I controller works by delayed action. It completely remedies
a loop error.
In order to calculate the value of the manipulated variable at a period of time n, the time up
until this period of time must be divided into small time slices. The loop errors at the end of each
time slice must be added up (integrated) and they are then entered in the calculation.
: Manipulated variable of the I controller at the time n
:Manipulated variable of the I controller at the time n-1; also called integral sum
:Gain of the I controller
Содержание xLogic
Страница 1: ......
Страница 2: ......
Страница 102: ...100 100 100 100 B B B B Blocks Blocks Blocks Blocks...
Страница 105: ...103 103 103 103 G G G G M M M M status status status status...
Страница 106: ...104 104 104 104 H H H H AM AM AM AM value value value value...
Страница 164: ...162 162 162 162 If the Memory Read block had been triggered the Q1 of ELC 12 CPU will be set 1...
Страница 204: ...202 202 202 202 Step Step Step Step 6 6 6 6 Moving Moving Moving Moving...
Страница 226: ...224 224 224 224...