44
Form E-564
Eastman
®
Fault
Message/Warning
Cause
Remedy
F532
Drive motor parameters
setup incomplete.
Before a motor can be enabled,
you must configure aminimum
set of parameters. These
parameters have not been config
-
ured.
Issue the command DRV.SETU
-
PREQLIST to display the list
of the parameters that youmust
configure. Configure these parame
-
ters either manually or automatically.
Parameters for BiSS analog, Endat,
or SFD feedback, are set automati
-
cally when MOTOR.AUTOSET is
set to 1 .
F534
Failed to read motor pa-
rameters from feedback
device.
Motor either does not have
motor feedback memory, or the
motor feedback memory is not
programmed properly so the
parameters cannot be read.
Try to read parameters again by
clicking the Disable and Clear
Faults button. If this attempt is not
successful, then set MOTOR.
AUTOSET to 0 and program the
parameters using the setup wizard
ormanually. If the motor has motor
memory (BiSS analog, Endat, and
SFD), return the motor to the
manufacturer to have the memory
programmed.
F535
Power-board over-tem-
perature fail.
The power-board temperature sensor
indicates more than 85 °C.
Reduce the load of the drive or
ensure better cooling.
F601
Modbus data rate is too
high.
Modbus controller data rate is
too high.
Reduce data rate.
F602
Safe torque off.
Safe torque off function has
been triggered.
Reapply supply voltage to STO if
safe to do so.
n603
OPMODE incompatible
with CMDSOURCE
This warning is generated when
the drive is enabled and the gearing
command source is selected at the
same time as torque or velocity op-
mode.
Select a different DRV.OPMODE
andDRV.CMDSOURCE combina
-
tion.
n604
EMUEMODE incompat
-
ible with DRV.HAND
-
WHEELSRC.
Emulated encode mode is incompat-
ible with the selected hand wheel
source.
ISelect a compatible emulated
encode mode or change handwheel
source.
F701
Fieldbus runtime.
Runtime communication fault.
Check fieldbus connections (X11),
settings, and control unit.
F702
n702
Fieldbus communication
lost.
All fieldbus communication was
lost.
Check fieldbus connections (X11),
settings, and control unit.
F703
Emergency timeout
occurred while axis
should disable
Motor did not stop in the timeout
defined.
Change timeout value, change
stop parameters, improve tuning.