27
•
Replace board if the problem persists.
•
Cycle the Power to Recover.
•
The flashing Alert/Alarm LED indications that
appear with a continuously illuminated Lockout
LED can be recovered from by cycling the power to
the IBC-3.1.
•
If the Lockout LED is illuminated without the
Alert/Error LED, this typically indicates that the
furnace is out of wood or the fire went out.
•
.P.O.S.T means Power-On Self-Test.
Technician Troubleshooting
Lockout/Standby
Lockout/Standby can occur for the following reasons: out of
wood, low Stack temperature for an extended period, and
thermocouple wired backwards.
Tripped Fuse
•
Check wiring and cables to insure that there are no
short circuits.
•
Check wiring and cables for cuts in the plastic
coating.
•
Check power to insure 120VAC.
•
Check load on the circuit.
•
Isolate issue before replacing the IBC-3.1 board.
No Power to the Board
•
Check wires from the IBC-3.1 board to the power
supply and replace if necessary and check the fuse
on the power supply and replace.