Section 4. Web Server Interface
4.31 Menu Items: Alarm Set- Alarm ON/OFF
The
Alarm Set- Alarm ON/OFF
page allows the user to enable or disable alarms related to:
▪
LOAD NFB #1-#10 OFF
: these are Load circuit breaker alarms that activate when any LOAD
breaker is turned OFF.
▪
BATT NFB#1 OFF and #2 OFF:
: these are the BATT. 1 and BATT.2 circuit breaker alarms that
activate when either BATT breaker is turned OFF.
▪
BATT CELL #1 Check and #2 Check
: these check the BATT Cell cables and alarms when voltages
are not read on either cable.
▪
BATT Sensor#1 Fail
: This is the Battery Temperature sensor and will alarm if it should be
plugged into the Shelf but is not connected.
▪
RACK Sensor Fail
: This is the Battery Temperature sensor and will alarm if it should be plugged
into the Shelf but is not connected.
▪
Battery Discharge:
this alarms anytime the Battery are discharing.
▪
LVD1 RELAY OPEN
: this alarms when external battery string(s) are connected, battery voltage is
above the LVD1 shutdown value, the Battery breaker is active but the LVD1 is not engaged.
▪
LVD2 RELAY OPEN
: this alarms when external battery string(s) are connected, battery voltage is
above the LVD2 shutdown value, the Battery breaker is active but the LVD2 is not engaged.
▪
Click the
Setting
button to capture any changes made in this page.
Figure 16n. Alarm Set- Alarm ON/OFF page