24
Eagle Eye Power Solutions, LLC | 877-805-3377 | www.eepowersolutions.com
Section 4. Web Server Interface
4.7 Menu Items: Operating Information- Setting Information
This page displays operating status based on configurable parameters in the
Configuration-
Operate Set
page or the
LVD Operate Set
page, including:
•
CHARGE MODE-
Battery Charge method is either Auto or Manual Float or Manual EQ (Boost)
•
FL VOLT-
Float Charge Voltage value (between 42V ~ 58V)
•
EQ VOLT-
Equalize (Boost) Charge Voltage value (between 42V ~ 58V)
•
AC Input Phase Select-
AC Input setting for either 1Phase or 3Phase
•
LVD1 Voltage Setting-
LVD1 contactor dropout voltage setpoint (between 42V ~ 54V)
•
LVD2 Voltage Setting-
LVD2 contactor dropout voltage setpoint (between 42V ~ 54V)
•
DATA LOG PERIOD-
setting for how often the Data Log updates (OFF or 1min ~ 1 Hour)
•
Sound Alarm ON/OFF-
Audible Alarm is either turned ON or turned OFF
See
Configuration-Operate Set
page or
LVD Operate Set
page for additional details
Figure 12a. Operating Information- Setting Information page