Section 4. Web Server Interface
4.11 Menu Items: Battery Information- Temperature Compensation
This page includes a temperature-compensated Battery Charge Profile that actively graphs the
values and slope of the battery charge voltage versus ambient temperature. The configurable
parameters are in the
Configuration- Temp Compensation
page and include:
•
Used/Unused
dropdown:
Used
sets Temperature Compensation ON (recommended
whenever Battery Banks are used);
Unused
sets Temperature Compensation OFF.
•
mV/Cell multiplier
for Temperature Compensation (use value listed in Battery
Manufacturer’s
datasheet).
•
# of Cells in -48V Battery String
= (24) for a typical VRLA string.
•
Minimum and Maximum Charge Temperatures
(use value listed in Battery
Manufacturer’s
datasheet).
See
Battery Manufacturer’s datasheet
for battery charge and related temperature
details.
Ensure Battery Temperature cables are connected properly between Shelf and Battery Bank(s)
Figure 13b. Battery Information- Temperature Compensation page