Section 4. Web Server Interface
4.30 Menu Items: Alarm Set- Digital Inputs Used Set
The
Alarm Set- Digital Inputs Used Set
page allows the
user to edit settings for the 6 External Alarm inputs.
The dropdown menu for Input Alarm1~ Input Alarm 6
includes 3 choices:
▪
Not Used
: Choose this setting when not connecting any wires to the 2-wire Alarm Input.
▪
Normal Close
: Choose this setting for the alarm to activate when the 2-wire Alarm input is
physically connected and will switch to open (such as a relay or a FET as a switch). In this
configuration and using a relay, the contacts are NC (Normally Closed) so only alarm when the
relay activates (contacts will be open).
▪
Normal Open
: Choose this setting for the alarm to activate when the 2-wire Alarm input is
physically connected and will switch to closed (such as a relay of a FET as a switch). In this
configuration and using a relay, the contacts are NO (Normally Open) so only alarm when the
relay activates (contacts will be closed).
▪
Click the
Setting
button to capture any changes made in this page.
▪
Additionally…
➢
Each of the 6 Digital Input alarm items can individually given a name, up to 12
characters long, in the
Digital Inputs Name Set
page
➢
Used Digital Input alarms are visible in the
Status Information-Alarm
page.
➢
Section 3.6
has details on the terminal block and wiring specifications.
Figure 16m. Alarm Set- Digital Inputs Used page