EAE Technology
www.eaetechnology.com
Page 53 / 80
(0% = top; 100% = button).
This parameters are configured the blind height and slat position. If the
“Forced operation
(1bit/2bit)”
is selected
“activated (1bit)”
,
“Position height/slat in [0…100]”
parameters are
visible.
Behavior after bus voltage return
*no forced position active
forced position ON, raising
forced position ON, lowering
state of forced pos. before bus volt. fail.
The forced position function can be initialized after bus voltage return so the forced operation
communication object is updated. After the bus voltage return, forced position function set to the
parametrized position.
▪
Set the parameter to “
no forced position active
”;
The forced operation is deactivated after bus voltage return.
▪
Set the parameter t
o “
forced position ON raising/lowering
”;
The forced operation active and the blind rising/lowering after bus voltage return.
▪
Set the parameter to “
state of forced pos. before bus volt. fail
”;
After bus voltage return, the forced position state last selected and internally stored in the
device. ETS download operation deletes the stored state.
4.5.4.4
A/B
–
Feedbacks