2
Communication Object Table
The device has 254 communication objects. Overview of all communication objects of the device can
be seen on the following table. Object names will be changed according to channel function as
follows.
Fan coil:
Fan A/B1, Fan C/D1, Fan E/F1, Fan G/H1, Fan I/J1 etc.
Valve control:
Valve A/B, Valve C/D, Valve E/F, Valve G/H, Valve I/J.
Shutter/Blind DC:
Output A/B, Output C/D, Output E/F, Output G/H, Output I/J.
Shutter/Blind AC:
Output A, Output B, Output C, Output D, Output E.
Switch:
Output A1, Output A2, Output B1, Output B2, Output C1, Output C2 etc.
No
Name
Function
DTP Type
Length
Flags
0
General
In operation
1.002
1 bit
CWT
1
General
Scene 8-bit
18.001
1 byte
CW
2
Blind
Wind alarm
1.005
1 bit
CWTU
3
Blind
Rain alarm
1.005
1 bit
CWTU
4
Blind
Frost alarm
1.005
1 bit
CWTU
5
Input a
Disable
1.003
1 bit
CW
6
Input a
Switch
1.001
1 bit
CWT
Switch
–
short
1.001
1 bit
CWT
Shutter Up/Down
1.008
1 bit
CT
Value (0,1)
1.001
1 bit
CWT
Value (forced)
2.001
2 bit
CWT
Value [0...255]
5.001
8 bit
CWT
Value [0...65535]
8.001
16 bit
CWT
Value [-32768...32767]
7.001
16 bit
CWT
Value [0...4294967295]
12.001
32 bit
CWT
7
Input a
Switch
–
long
1.001
1 bit
CWT
Dimming brighter / darker
3.007
4 bit
CT
Shutter stop / lamella
1.007
1 bit
CT
Value (0,1) - long
1.001
1 bit
CT
Value (forced) - long
2.001
1 bit
CT
Value [0...255] - long
5.001
8 bit
CT
Value [0...65535] - long
8.001
16 bit
CT
Value [-32768...32767]
7.001
16 bit
CT
Value [0...4294967295]
12.001
32 bit
CT
8
Input a
Shutter upper limit position
1.002
1 bit
CW
Value (temperature)
14.068
32 bit
CT
9
Input a
Shutter lower limit position
1.002
1 bit
CW
Value (temperature) - long
14.068
32 bit
CT
10
…
94
Input b … s
Same as
“
Input a
”
95
Output A1
Switch
1.001
1 bit
CW
Output A
Output A/B
Move blind/shutters up-down
1.008
1 bit
CW
Fan A/B1
Fan speed switch
5.010
1 byte
CW
Control input
Control value HEATING
5.001
1 byte
CW