Product Manual RCUXXYY
EAE KNX Room Control Unit
RCUXXYY PM R1.0
©
EAE Technology
www.eaetechnology.com
Page 56 / 80
Operation HEATING/COOLING after
bus voltage recovery
*unchanged bus return
heating
cooling
This parameter is used to select reaction after bus voltage recovery.
Object value for HEATING the object
“Toggle HEATING/COOLING”
0
*1
This parameter is used to which communication object value used for HEATING.
▪
Set the parameter to “0”
;
When the telegram is received “0”, HEATING operation is activated. (COOLING is
deactivated)
▪
Set the parameter to “1”
;
When the telegram is
received “1”, HEATING operation is activated. (COOLING is
deactivated)
Monitoring control valves
yes
*no
This parameter activate the thermostat monitoring. If the parameter selected
enable
,
Monitoring
period time in s [30…65535]
parameter is visible.
Monitoring period time
in s[30…65535]
30…
*120
…65535
The telegram of the active thermostat can be monitored cyclically. The device then expect a telegram
from the thermostat within the cycle time.
Send object value
(“Control value fault” 1 bit
)
no
*after change
after request
after change or request
If the telegram is not received within the monitoring period time, it can be assumes that the sensor is
break or bus line interrupted. This object is sent the KNX bus.
The “Control value fault” can be used as an active or passive communication object. Active message
object, the switch status telegram is transmitted to the bus automatically when a state changes.
Passive status object, there is no telegram transmission after state changes. If you want to learn
switch status, you must read communication object. Communication object flags are automatically
set by ETS.
Enable control value after fault
yes
*no
This parameter activate the fault condition after fault operation. If the parameter selected
yes
,
Control value after fault in % [0…100] parameter is visible.
Control value after fault
in %[0…100]
0…
*30
…100
After the fault operation occurred in emergency state, the valve can be set the valve fault
percentage.