4
5
Rain alarm
Frost alarm
Active weather sensors can be monitored cyclically. The device expects a telegram from sensor within
the cycle time. If the telegram doesn’t receive within the cycle time or the value 1 is received, the blinds
are moved to parameterized position. The blind control telegrams are ignored until the device is
received telegram value 0.
The monitoring period is restarted each telegram is received from weather sensor. The wind alarms are
connected each other via OR gate.
The object is;
0 = no alarm
1 = alarm active
6.2
Input Object Description
No
Object name
Name
DTP Type
Length
Flags
5
Disable
Input a
DPT 1.003
1 bit
CW
0: enable input
1: disable input
This object is only visible if it is used as an input. Via the group address linked to this object blocking of
the respective input channel is turned on or off.
When a disabled input is enabled, no telegrams are sent on the bus, even if the state of the input has
changed during blocking. If the input is just being operated as it is being enabled, the input behaves as if
the operation has just commenced.
6
Switch
Switch - short
Input a
DPT 1.001
1 bit
CWT
0: OFF
1: ON
Switching telegrams are sent via the group address linked with this object. Object can be switched by
actuation of the ON, OFF or TOGGLE input.
6
Shutter up/down
Input a
DPT 1.008
1 bit
CT
The driving object is
for moving the shutters “move UP” and “move DOWN”.
0: Move upwards (UP)
1: Move downwards (DOWN)
6
Value
Input a
…
…
CWT