Product Manual RCUXXYY
EAE KNX Room Control Unit
RCUXXYY PM R1.0
©
EAE Technology
www.eaetechnology.com
Page 73 / 80
This object is ;
0 = relay OFF position
1 = relay ON position
97
Enable staircase function
Output A1
DPT 1.003
1 bit
CRW
This object is used to activation of the staircase function. This object is enabled, the staircase function is
activated.
The object is;
0 = disable
1 = enable
98
Staircase lighting duration
Output A1
DPT 7.007
2 byte
CRW
The staircase lighting duration is set via this object. The object resolution is second. In addition, the bus
return state can be parameterized by the parameter at the
staircase function
tag.
The object is;
0 = must be greater than zero
….
65535
99
Permanent ON
Output A1
DTP 1.001
1 bit
CW
This object is used to mask the other function. This meanings function is working back ground of the
Permanent ON. If the Permanent ON object is set to off, the other function switch result can be visible
on the output. After bus voltage return, the object is deactivated.
This object feature is useful for cleaning person.
The object is;
0 = permanent ON active
1 = deactivate
100
External logic input
Output A1
DPT 1.001
1 bit
CW
This object is used to receive the switching data for the second input. The switch operation and external
logic are respect with logic OR, AND.
The object is;
0 = logic state
1 = logic state
101
Forced positioning
Output A1
DPT 2.001
2 bit
CW
This object is used to the switching state of the output is directly determined by this object. The first bit
is switching state and the second bit is activated or deactivated the forced control.
Bit Field
Description
Bit 0
:
Switching state “0”: switching off “1”: switching on
Bit 1 :
Forced control “0”: inactive “1”: active
102
Sweep
Output A1
DPT 1.017
1 bit
CW
This object is used to trigger the sweep function.