ET DC BLUE ADVANCED INSTALLER 2012.025.12.05.2014
14
PROGRAMMING
Open and closed limit position setup and door load profiling.
From Standby Mode
Action
Response
To enter the program
menu. Press and hold SET
button until buzzer beeps
twice.
Display begins flashing “P”
and buzzer beeps twice
to confirm the main
program menu is active.
Scroll up with the UP
button until “L” flashes.
Display flashes “L” to
confirm limit setup mode
is selected.
Press and release SET
button to begin limit
setup.
Buzzer beeps once and
“O” displays to indicate
open limit position must
be set.
Press and hold the UP
button to raise the door to
the required open
position.
The “n” symbol displays as
the door opens.
Fine tune using the UP
and DOWN buttons.
The “n” and “u” symbols
confirm the door direction
while fine tuning.
or
When satisfied the door is
in the correct open
position, press the SET
button to advance to the
close limit setup.
The buzzer beeps once
and the “C” symbol
displays to indicate the
closed limit position must
be set.
Press and hold the DOWN
button to lower the door
to the required closed
position.
The “u” symbol displays as
the door closes.
Fine tune using the UP
and DOWN buttons.
The “n” and “u” symbols
confirm the door direction
while fine tuning.
or
When satisfied the door is
in the correct closed
position, press the SET
button to advance to the
automatic door load
profiling stage.
Door opens and closes
again.
The display confirms the
direction and the buzzer
will beep intermittently as
the motor runs.
When complete, the
control returns to the main
program menu.
Display = Flashing “P” and
buzzer beeps once.
Scroll up or down
to next program
option.
OR
Press and release EXIT to
return to Standby mode.
See Note 1 on page 13!!!