User Manual EE431
Duct and Immersion Temperature Sensor | 14
5.4.2. Device Address
Address Switch
Address setting via EE-PCS Product Configuration Software
All DIP switches at position 0
address has to be set via EE-PCS.
(factory
setting)
Modbus
(slave device):
Factory setting 66 (permitted values: 1…247).
BACnet
(master device):
Factory setting 66 (permitted values: 0…127).
Example: 0000 0000 = Address is set via configuration software.
0 0 0 0 0 0 0 0
0
1
Address Switch
Address setting via DIP switch
Modbus
(slave device): Setting the DIP switches to any other address than 0,
overrules the Modbus address set via EE-PCS (permitted values: 1…247).
BACnet
(master device): Setting the DIP switches to any other address than 0,
overrules the BACnet address set via configuration software
.
BACnet Note: permitted values are 0…127. The 8th bit of the DIP switches is
ignored (ID 127 = 0111 111). To set address 0 via DIP switches, the 8th bit shall
be set to 1 (ID 0 = 1000 0000).
Example: 0000 1011 binary = Address set to 11.
1 1 0 1 0 0 0 0
0
1
5.4.3. BACnet MS/TP Setup
Refer to PICS (Product Implementation Conformance Statement) - available on
www.epluse.com/ee431
.
5.4.4. BACnet MS/TP Protocol Settings
Factory settings
User selectable values
(via EE-PCS / BACnet MS/TP protocol)
Baud rate
As per type number ordered
9 600, 19 200, 38 400, 57 600, 76 800, 115 200
Data bits
8
8
Parity
None
None
Stop bits
1
1
BACnet address
66
0…127
Tab. 5
BACnet protocol settings
PLEASE NOTE
The recommended settings for multiple devices in a BACnet MS/TP network are 38 400, 8, none, 1.
The EE4x1D PICS (Product Implementation Conformance Statement) are available on the E+E website at
www.epluse.com/ee431
.
BACnet address and baud rate can be set via:
▪
EE-PCS Product Configuration Software and the USB configuration adapter HA011066.
▪
BACnet protocol, see the PICS.