User Manual EE431
Duct and Immersion Temperature Sensor | 10
4.1 Duct Mounting
4.1.1. Mounting with flange
▪
Mount the sensor about one meter from the inlet
▪
Mount the probe in a way, that the probe tip is placed in the middle of the duct
Ø > 16
Ø > 0.63
6
0.24
60
±0.3
2.36
±0.11
Fig. 3
Correct position of the probe in a flange
4.1.2. Minimum Immersion Depth
Placement options
Temperature sensor
Flow
Temperature sensor
Min. 50 mm (1,97")
Temperature sensor
Flow
Temperature sensor
Min. 50 mm (1,97")
Fig. 4
Correct position in a pipe
4.1.3. Mounting with Immersion Well
1.
2.
Fig. 5
Handling of the immersion well
Procedure:
1.
The spring inside the well must be removed and replaced by a standard M12x1.5 cable gland
(not included in the scope of supply).
2.
Insert the sensor and fix it by fastening the cable gland.
NOTICE
Observe the operating temperature range of the cable gland to match the process parameters.