User Manual EE431
Duct and Immersion Temperature Sensor | 13
5.1.2. PCS10 Product Configuration Software
For sensor adjustment and for changing the settings, please proceed as follows:
1.
Download the PCS10 Product Configuration Software from
2.
Connect the E+E device to the PC using the USB configuration adapter.
3.
Start the PCS10 software.
4.
Follow the instructions on the PCS10 opening page for scanning the ports and identifying the connected
device.
5.
Click on the desired setup or adjustment mode from the main PCS10 menu on the left and follow the online
instructions of the PCS10.
5.2 EE431 analogue with HA011023
Use the PCS10 and the HA011023 USB Configuration Adapter for EE431 with analogue output. An external
power supply according to the technical data is required. The power supply adapter V03 is suitable. As soon as
the device is connected to the adapter, the display shows CAL.
With the PCS10, the output scaling, the output measuring unit and the displayed unit (°C or °F) can be changed
.
Upper and lower thresholds can be set up for the measurands. The display flashes at one-second interval for
measured T beyond the range.
An offset (Fig. 11) and a 1- or 2-point adjustment
(Fig. 12) can be performed, as well as a reset to the factory
adjustment and settings. Besides, the configuration settings can also be exported or imported.
Fig. 7
HA011023 USB Configuration Adapter for EE431 with analogue output
5.3 EE431 analogue with EE-PCA and HA011065
Use the EE-PCS and EE-PCA with the connection cable HA011065. For further details see datasheet EE-PCA
(available at
).
With the PCS10, the output scaling, the output measuring and the displayed unit (°C or °F) can be changed
.
An offset (Fig. 11) and a 1- or 2-point adjustment (Fig. 12)
can be performed, as well as a reset to the factory
adjustment and settings. Besides, the configuration settings can also be exported or imported.
5.4 EE431 with RS485 Digital Interface
Use the EE-PCS and the USB configuration adapter HA011066.
With the EE-PCS, an offset adjustment (Fig. 11) and
1- or 2-point adjustment (Fig. 12) can be performed.
The temperature adjustment can be reset to the factory settings. In addition, further digital configuration settings
can be made (see below).
5.4.1. Hardware Bus Termination
The bus termination can be realized with 120 Ω resistor (slide switch on the board).