17
Operating instructions for EE360 Moisture in Oil
Parity
None
Odd
Even
Baudrate
value
value
value
Stop bits
Address
Menu
Modbus
settings*
* Menu only available with connected Modbus RTU module during EE360 start-up.
Data transmission
Factory settings
Selectable values
Baud rate
9600
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 76800
Data bits
8
8
Parity
EVEN
None, odd, even
Stop bits
1
1 or 2
Slave address
231
1...247
The recommended setting for multiple devices in a Modbus RTU network is 9600 8 Even 1.
4.4 Ethernet Module - Modbus tCP (option J4)
The Ethernet module features power over Ethernet (PoE) and RJ45 connector with IP65
protection class.
The Ethernet connection must be disconnected before opening the housing!
Due to strong self-heating effects, the Ethernet interface is available only for the types T2, T5 and
T10 (duct mount and remote probe). Wall mount applications with Ethernet interface shall be realized
with.type.T5.and.0.5m.probe.cable.by.fixing.the.probe.onto.the.wall.with.the.mounting.bracket.type.
HA010211
4.4.1 Available tCP and UDP ports
Modbus tCP (Port 502)
See “Modbus TCP/IP implementation guide” which can be found on http://www.modbus.org/docs/Mod-
bus_Messaging_Implementation_Guide_V1_0b.pdf
The.unit.identifier.of.the.MBAP.header.is.not.used.and.can.be.any.value.from.0.to.255