Operating instructions for EE310 Humidity / Temperature Transmitter
Parity
None
Odd
Even
Baudrate
value
value
value
Stop bits
Address
Menu
Modbus
settings*
* Menu only available with connected Modbus RTU module during EE310 start-up.
Data transmission
Factory settings
Selectable values
Baud rate
9600
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 76800
Data bits
8
8
Parity
EVEN
None, odd, even
Stop bits
1
1 or 2
Slave address
231
1...247
The recommended setting for multiple devices in a Modbus RTU network is 9600 8 Even 1.
4.4 Modbus Map
Register
[DEC]
Protocol
address [HEX]
Measured value
Unit
Type
Read registers: function code 0x03 / 0x04
31021
3FC
Relative humidity
%
32-bit float
31003
3EA
Temperature
°C
32-bit float
31005
3EC
Temperature
°F
32-bit float
31105
450
Dew point temperature
°C
32-bit float
31107
452
Dew point temperature
°F
32-bit float
31131
46A
Frost point / Dew point temperature
°C
32-bit float
31133
46C
Frost point / Dew point temperature
°F
32-bit float
31113
458
Absolute humidity
g/m
3
32-bit float
31115
45A
Absolute humidity
gr/ft
3
32-bit float
31121
460
Mixing ratio
g/kg
32-bit float
31123
462
Mixing ratio
gr/lb
32-bit float
31109
454
Wet bulb temperature
°C
32-bit float
31111
456
Wet bulb temperature
°F
32-bit float
31125
464
Specific enthalpy
kJ/kg
32-bit float
31129
468
Specific enthalpy
BTU/lb
32-bit float
31127
466
Specific enthalpy
ft lbf/lb
32-bit float
31101
44C
Water vapour partial pressure
mbar
32-bit float
31103
44E
Water vapour partial pressure
psi
32-bit float
31151
47E
Volume concentration
ppm
32-bit float
35001
1388
Air pressure
mbar
32-bit float
Write registers: function code 0x06 for 16-bit and 0x10 (decimal: 16) for 32-bit
0001
0
Slave-ID
/
16-bit integer
5001
1388
Air pressure
mbar
32-bit float